APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 45 of 72)
ADDR
REGISTER NAME
9010
FlexElement 1 Reset Delay
9011
FlexElement 1 Block
9013
FlexElement 1 Target
9014
FlexElement 1 Events
9015
...Repeated for FlexElement 2
902A
...Repeated for FlexElement 3
903F
...Repeated for FlexElement 4
9054
...Repeated for FlexElement 5
9069
...Repeated for FlexElement 6
907E
...Repeated for FlexElement 7
9093
...Repeated for FlexElement 8
90A8
...Repeated for FlexElement 9
90BD
...Repeated for FlexElement 10
90D2
...Repeated for FlexElement 11
90E7
...Repeated for FlexElement 12
90FC
...Repeated for FlexElement 13
9111
...Repeated for FlexElement 14
9126
...Repeated for FlexElement 15
913B
...Repeated for FlexElement16
Fault Report Settings (Read/Write Setting) (up to 5 modules)
9200
Fault Report 1 Source
9201
Fault Report 1 Trigger
9203
Fault Report 1 Z1 Magnitude
9204
Fault Report 1 Z1 Angle
9205
Fault Report 1 Z0 Magnitude
9206
Fault Report 1 Z0 Angle
9207
Fault Report 1 Line Length Units
9208
Fault Report 1 Line Length
9209
Fault Report 1 VT Substitution
920A
Fault Report 1 System Z0 Magnitude
9208
Fault Report 1 System Z0 Angle
920C
Fault REM1-TAP Z1 Magnitude
920D
Fault REM1-TAP Z1 Angle
920E
Fault REM1-TAP Length
920F
Fault REM2-TAP Z1 Magnitude
9210
Fault REM2-TAP Z1 Angle
9511
Fault REM2-TAP Length
9212
...Repeated for Fault Report 2
9224
...Repeated for Fault Report 3
9236
...Repeated for Fault Report 4
9248
...Repeated for Fault Report 5
dcmA Outputs (Read/Write Setting) (24 modules)
9360
dcmA Output 1 Source
9361
dcmA Output 1 Range
9362
dcmA Output 1 Minimum
9364
dcmA Output 1 Maximum
9366
...Repeated for dcmA Output 2
936C
...Repeated for dcmA Output 3
9372
...Repeated for dcmA Output 4
9378
...Repeated for dcmA Output 5
937E
...Repeated for dcmA Output 6
9384
...Repeated for dcmA Output 7
938A
...Repeated for dcmA Output 8
9390
...Repeated for dcmA Output 9
GE Multilin
RANGE
0 to 65.535
0 to 65535
0 to 2
0 to 1
0 to 5
0 to 4294967295
0.01 to 250
25 to 90
0.01 to 650
25 to 90
0 to 1
0 to 2000
0 to 2
0.01 to 650.00
25 to 90
0.01 to 250
25 to 90
0 to 2000
0.01 to 250
25 to 90
0 to 2000
0 to 65535
0 to 2
–90 to 90
–90 to 90
D60 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
s
0.001
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F167
---
1
F300
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
1
F147
0.1
F001
---
1
F270
ohms
0.01
F001
degrees
1
F001
ohms
0.01
F001
degrees
1
F001
---
0.1
F001
ohms
0.01
F001
degrees
1
F001
---
0.1
F001
---
1
F600
---
1
F522
pu
0.001
F004
pu
0.001
F004
DEFAULT
0
0
0 (Self-reset)
0 (Disabled)
B
0 (SRC 1)
0
300
75
900
75
0 (km)
1000
0 (None)
900
75
300
75
1000
300
75
1000
0
0 (–1 to 1 mA)
0
1000
B-53