13.4 End position guiding
The actuator stem moves to the end positions early if the end position guiding function is ac-
tive:
13.4.1 Operating direction increasing/increasing
− End position guiding: valve open (c35): The actuator stem moves the valve to the top
end position if the input signal reaches the value entered in this code. Setting c35 =
100.0 % causes this function (end position guiding: valve open) with a retracting actuator
stem to be deactivated.
− End position guiding: valve closed (c36): The actuator stem moves the valve to the lower
end position if the input signal reaches the value entered in this code. Setting c36 =
0.0 % causes this function (end position guiding: valve closed) with an extending actuator
stem to be deactivated.
13.4.2 Operating direction increasing/decreasing
− End position guiding: valve open (c35): The actuator stem moves the valve to the lower
end position if the input signal reaches the value entered in this code. Setting c35 =
100.0 % causes this function (end position guiding: valve open) with a retracting actuator
stem to be deactivated.
− End position guiding: valve closed (c36): The actuator stem moves the valve to the top
end position if the input signal reaches the value entered in this code. Setting c36 =
0.0 % causes this function (end position guiding: valve closed) with an extending actuator
stem to be deactivated.
Code
Description
c35
End position guiding: valve open
c36
End position guiding: valve closed
EB 8331-4 EN
WE
Adjustment range
97.0 %
50.0 to 100.0 %
1.0 %
0.0 to 49.9 %
Configuration level
41