Level application example

The application is a vessel that takes an average 3 hours to fill and 3 weeks to empty.
Fill rate = 0.08 m/minute (Low Cal Pt. minus High Cal Pt.) / fastest fill/empty time
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
SITRANS LR250
Level
Quick Start Setting
MATERIAL
RESPONSE RATE
UNITS
OPERATION
LOW CALIBRATION POINT
HIGH CALIBRATION POINT
APPLY? (CHANGES)

Auto False Echo Suppression

If SITRANS LR250 displays a false high level, or the reading is fluctuating between the
correct level and a false high level, you can use the Auto False Echo Suppression
parameters to prevent false echo detection. See
setup
for instructions.
Page 36
SITRANS LR250 (HART) – INSTRUCTION MANUAL
Sensor
Reference
1.0 m
Point
High
Calibration
Point
15.5 m
Low
Calibration
Point
LIQUID
SLOW
Response rate = 0.1 m/minute.
m
LEVEL
Material level referenced from Low Calibration Point.
15.5
Process empty level.
1.0
Process full level.
YES
Save new settings.
2.2.5. TVT (Auto False Echo Suppression)
Description
7ML1998JE01

Advertisement