Siemens SINAMICS V90 Operating Manual page 49

Hide thumbs Also See for SINAMICS V90:
Table of Contents

Advertisement

The PZD in green indicates that it has a bit definition. You can read the binary value of each
bit from the table.
Supported telegrams
SINAMICS V90 PN supports standard telegrams and Siemens telegrams for speed control
mode. You can select the desired telegram with parameter p0922. See the following table for
details.
From the perspective of the drive unit, the received process data represents the receive
words and the process data to be sent to the send words.
Telegram
Standard telegram 1
Standard telegram 2
Standard telegram 3
Standard telegram 5
Standard telegram 7
Standard telegram 9
Siemens telegram 102
Siemens telegram 105
Standard telegram 110
Standard telegram 111
One PZD = one word
Standard telegram 5 and Siemens telegram 105 can only be used when the V90 PN connects to the SIMATICS S7-1500
and the TIA Portal version is V14 or higher.
SINAMICS V-ASSISTANT Online Help
Operating Manual, 04/2017, A5E36618042-003
Maximum number of PZD
Receive word
2
4
5
9
2
10
6
10
12
12
Send word
2
4
9
9
2
5
10
10
7
12
Task navigation
Description
p0922 = 1
p0922 = 2
p0922 = 3
p0922 = 5
p0922 = 7
p0922 = 9
p0922 = 102
p0922 = 105
p0922 = 110
p0922 = 111
49

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents