4.4.3.3

Manual tuning

When the auto tuning function cannot reach the expected tuning results, you can disable the
auto tuning function by setting the parameter p29021 and manually perform tuning:
● p29021=5: auto tuning function is disabled and all control parameters are reset to tuning
default values.
● p29021=0: auto tuning function is disabled without changing control parameters.
Parameter settings
You can set the parameters on the following panel:
Click
default values of the parameters are different when you use the different drives and motors.
The function of the button is not drive default so the tuning default values of the control
parameters are different with their factory settings.
● p1414
● p1415
● p1656
● p1658
● p1659
● p2533
● p29110[0]
SINAMICS V-ASSISTANT Online Help
Operating Manual, 04/2017, A5E36618042-003
to reset the following parameters to their tuning defaults. The tuning
Task navigation
117