GE D30 Instruction Manual page 276

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5.6 GROUPED ELEMENTS
5
Figure 5–73: PHASE INSTANTANEOUS OVERCURRENT TIMING CURVES
ETT NG
PHASE IOC1
FUNCTION:
Enabled = 1
Disabled = 0
ETT NG
PHASE IOC1
SOURCE:
IA
IB
IC
ETT NG
PHASE IOC1
BLOCK-A:
Off = 0
ETT NG
PHASE IOC1
BLOCK-B:
Off = 0
ETT NG
PHASE IOC1
BLOCK-C:
Off = 0
Figure 5–74: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC
5-144
ETT NG
ETT NG
PHASE IOC1
PHASE IOC1
PICKUP:
PICKUPDELAY:
AND
RUN
PHASE IOC1 RESET
DELAY:
IA ≥ PICKUP
t
PKP
t
AND
RUN
RST
t
IB ≥ PICKUP
PKP
t
RST
AND
RUN
t
PKP
IC ≥ PICKUP
t
RST
D30 Line Distance Protection System
5 SETTINGS
FLEXLOG C
OPE AND
PHASE IOC1 A PKP
PHASE IOC1 A DPO
PHASE IOC1 B PKP
PHASE IOC1 B DPO
PHASE IOC1 C PKP
PHASE IOC1 C DPO
PHASE IOC1 A OP
PHASE IOC1 B OP
PHASE IOC1 C OP
OR
PHASE IOC1 PKP
OR
PHASE IOC1 OP
AND
PHASE IOC1 DPO
827033A6.VSD
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents