GE D30 Instruction Manual page 241

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
GROUPED ELEMENTS
 LINE PICKUP
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The line pickup feature uses a combination of undercurrent and undervoltage to identify a line that has been de-energized
(line end open). Alternately, the user may assign a FlexLogic™ operand to the
minal status. Three instantaneous overcurrent elements are used to identify a previously de-energized line that has been
closed onto a fault. Faults other than close-in faults can be identified satisfactorily with the distance elements.
Co-ordination features are included to ensure satisfactory operation when high speed automatic reclosure (AR) is
employed. The
AR CO-ORD DELAY
reclose. Co-ordination is achieved by all of the
times out. The
CO-ORD DELAY
implemented.
The line pickup protection incorporates zone 1 extension capability. When the line is being re-energized from the local ter-
minal, pickup of an overreaching zone 2 or excessive phase current within eight power cycles after the autorecloser issues
a close command results in the
GE Multilin
SETTING GROUP 1(6)
LINE PICKUP
FUNCTION: Disabled
LINE PICKUP SIGNAL
SOURCE: SRC 1
PHASE IOC LINE
PICKUP: 1.000 pu
LINE PICKUP UV PKP:
0.700 pu
LINE END OPEN PICKUP
DELAY:
0.150 s
LINE END OPEN RESET
DELAY:
0.090 s
LINE PICKUP OV PKP
DELAY:
0.040 s
AR CO-ORD BYPASS:
Enabled
AR CO-ORD PICKUP
DELAY:
0.045 s
AR CO-ORD RESET
DELAY:
0.005 s
TERMINAL OPEN:
Off
AR ACCELERATE:
Off
LINE PICKUP DISTANCE
TRIP: Enabled
LINE PICKUP BLOCK:
Off
LINE PICKUP
TARGET: Self-reset
LINE PICKUP
EVENTS: Disabled
setting allows the overcurrent setting to be below the expected load current seen after
LINE PICKP UV
setting is normally enabled. It is disabled if high speed autoreclosure is
AR CO-ORD BYPASS
FlexLogic™ operand. For security, the overcurrent trip is supervised
LINE PICKUP RCL TRIP
D30 Line Distance Protection System

LINE PICKUP
Range: Disabled, Enabled
Range: SRC 1, SRC 2
Range: 0.000 to 30.000 pu in steps of 0.001
Range: 0.000 to 3.000 pu in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Disabled, Enabled
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
TERMINAL OPEN
elements resetting and blocking the trip path before the
5.6 GROUPED ELEMENTS
5.6.3 LINE PICKUP
setting that specifies the ter-
AR
5-109