Specifications; Protection Elements - GE D30 Instruction Manual

Line distance protection system
Hide thumbs Also See for D30:
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.2SPECIFICATIONSSPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE
The operating times below include the activation time of a trip rated form-A output contact unless otherwise indi-
cated. FlexLogic™ operands of a given element are 4 ms faster. This should be taken into account when using
NOTE
FlexLogic™ to interconnect with other protection or control elements of the relay, building FlexLogic™ equations, or
interfacing with other IEDs or power system devices via communications or different output contacts.
PHASE DISTANCE
Characteristic:
mho (memory polarized or offset) or
quad (memory polarized or non-direc-
tional), selectable individually per zone
Number of zones:
3
Directionality:
forward, reverse, or non-directional per
zone
Reach (secondary ):
0.02 to 500.00  in steps of 0.01
Reach accuracy:
±5% including the effect of CVT tran-
sients up to an SIR of 30
Distance:
Characteristic angle:
30 to 90° in steps of 1
Comparator limit angle: 30 to 90° in steps of 1
Directional supervision:
Characteristic angle:
30 to 90° in steps of 1
Limit angle:
30 to 90° in steps of 1
Right blinder (Quad only):
0.02 to 500  in steps of 0.01
Reach:
Characteristic angle:
60 to 90° in steps of 1
Left Blinder (Quad only):
0.02 to 500  in steps of 0.01
Reach:
Characteristic angle:
60 to 90° in steps of 1
Time delay:
0.000 to 65.535 s in steps of 0.001
Timing accuracy:
±3% or 4 ms, whichever is greater
Current supervision:
Level:
line-to-line current
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
VT location:
all delta-wye and wye-delta transformers
CT location:
all delta-wye and wye-delta transformers
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
GE Multilin
PHASE DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part
of the relay. See output contacts specifications for estimation of
the total response time for a particular application. The operating
times are average times including variables such as fault inception
angle or type of a voltage source (magnetic VTs and CVTs).
30
25
20
15
10
5
0
0%
D30 Line Distance Protection System

2.2 SPECIFICATIONS

2.2.1 PROTECTION ELEMENTS

Phase Element (21P)
10%
20%
30%
40%
50%
60%
Fault Location [%]
2
SIR = 0.1
SIR = 1
SIR = 10
SIR = 20
SIR = 30
70%
80%
837717A1.CDR
2-9