Advertisement

5.5 FLEXLOGIC™
The operands available for this relay are listed alphabetically by types in the following table.
Table 5–7: D30 FLEXLOGIC™ OPERANDS (Sheet 1 of 8)
OPERAND TYPE
OPERAND SYNTAX
CONTROL
CONTROL PUSHBTN 1 ON
PUSHBUTTONS
CONTROL PUSHBTN 2 ON
CONTROL PUSHBTN 3 ON
CONTROL PUSHBTN 4 ON
CONTROL PUSHBTN 5 ON
CONTROL PUSHBTN 6 ON
CONTROL PUSHBTN 7 ON
DIRECT DEVICES
DIRECT DEVICE 1On
DIRECT DEVICE 16On
DIRECT DEVICE 1Off
DIRECT DEVICE 16Off
DIRECT INPUT/
DIR IO CH1 CRC ALARM
OUTPUT
CHANNEL
DIR IO CH2 CRC ALARM
MONITORING
DIR IO CH1 UNRET ALM
DIR IO CH2 UNRET ALM
ELEMENT:
AR1 ENABLED
Autoreclose
AR1 RIP
(per CT bank)
AR1 LO
AR1 BLK FROM MAN CLS
AR1 CLOSE
AR1 SHOT CNT=0
AR1 SHOT CNT=1
5
AR1 SHOT CNT=2
AR1 SHOT CNT=3
AR1 SHOT CNT=4
AR1 DISABLED
ELEMENT:
AUX OV1 PKP
Auxiliary
AUX OV1 DPO
overvoltage
AUX OV1 OP
AUX OV2 to AUX OV3
ELEMENT:
AUX UV1 PKP
Auxiliary
AUX UV1 DPO
undervoltage
AUX UV1 OP
AUX UV2 to AUX UV3
ELEMENT:
BKR ARC 1 OP
Breaker arcing
BKR ARC 2 OP
5-88
OPERAND DESCRIPTION
Control pushbutton 1 is being pressed
Control pushbutton 2 is being pressed
Control pushbutton 3 is being pressed
Control pushbutton 4 is being pressed
Control pushbutton 5 is being pressed
Control pushbutton 6 is being pressed
Control pushbutton 7 is being pressed
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
The rate of direct input messages received on channel 1 and failing the CRC
exceeded the user-specified level.
The rate of direct input messages received on channel 2 and failing the CRC
exceeded the user-specified level.
The rate of returned direct input/output messages on channel 1 exceeded the
user-specified level (ring configurations only).
The rate of returned direct input/output messages on channel 2 exceeded the
user-specified level (ring configurations only).
Autoreclose 1 is enabled
Autoreclose 1 is in progress
Autoreclose 1 is locked out
Autoreclose 1 is temporarily disabled
Autoreclose 1 close command is issued
Autoreclose 1 shot count is 0
Autoreclose 1 shot count is 1
Autoreclose 1 shot count is 2
Autoreclose 1 shot count is 3
Autoreclose 1 shot count is 4
Autoreclose 1 is disabled
Auxiliary overvoltage element has picked up
Auxiliary overvoltage element has dropped out
Auxiliary overvoltage element has operated
Same set of operands as shown for AUX OV1
Auxiliary undervoltage element has picked up
Auxiliary undervoltage element has dropped out
Auxiliary undervoltage element has operated
Same set of operands as shown for AUX UV1
Breaker arcing current 1 has operated
Breaker arcing current 2 has operated
D30 Line Distance Protection System