B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 18 of 51)
ADDR
REGISTER NAME
5901
Phase Time Overcurrent 1 Signal Source
5902
Phase Time Overcurrent 1 Input
5903
Phase Time Overcurrent 1 Pickup
5904
Phase Time Overcurrent 1 Curve
5905
Phase Time Overcurrent 1 Multiplier
B
5906
Phase Time Overcurrent 1 Reset
5907
Phase Time Overcurrent 1 Voltage Restraint
5908
Phase TOC 1 Block For Each Phase (3 items)
590B
Phase Time Overcurrent 1 Target
590C
Phase Time Overcurrent 1 Events
590D
Reserved (3 items)
5910
...Repeated for Phase Time Overcurrent 2
5920
...Repeated for Phase Time Overcurrent 3
5930
...Repeated for Phase Time Overcurrent 4
5940
...Repeated for Phase Time Overcurrent 5
5950
...Repeated for Phase Time Overcurrent 6
Phase Instantaneous Overcurrent (Read/Write Grouped Setting) (12 modules)
5A00
Phase Instantaneous Overcurrent 1 Function
5A01
Phase Instantaneous Overcurrent 1 Signal Source
5A02
Phase Instantaneous Overcurrent 1 Pickup
5A03
Phase Instantaneous Overcurrent 1 Delay
5A04
Phase Instantaneous Overcurrent 1 Reset Delay
5A05
Phase IOC1 Block For Phase A
5A06
Phase IOC1 Block For Phase B
5A07
Phase IOC1 Block For Phase C
5A08
Phase Instantaneous Overcurrent 1 Target
5A09
Phase Instantaneous Overcurrent 1 Events
5A0A
Reserved (6 items)
5A10
...Repeated for Phase Instantaneous Overcurrent 2
5A20
...Repeated for Phase Instantaneous Overcurrent 3
5A30
...Repeated for Phase Instantaneous Overcurrent 4
5A40
...Repeated for Phase Instantaneous Overcurrent 5
5A50
...Repeated for Phase Instantaneous Overcurrent 6
5A60
...Repeated for Phase Instantaneous Overcurrent 7
5A70
...Repeated for Phase Instantaneous Overcurrent 8
5A80
...Repeated for Phase Instantaneous Overcurrent 9
5A90
...Repeated for Phase Instantaneous Overcurrent 10
5AA0
...Repeated for Phase Instantaneous Overcurrent 11
5AB0
...Repeated for Phase Instantaneous Overcurrent 12
Neutral Time Overcurrent (Read/Write Grouped Setting) (6 modules)
5B00
Neutral Time Overcurrent 1 Function
5B01
Neutral Time Overcurrent 1 Signal Source
5B02
Neutral Time Overcurrent 1 Input
5B03
Neutral Time Overcurrent 1 Pickup
5B04
Neutral Time Overcurrent 1 Curve
5B05
Neutral Time Overcurrent 1 Multiplier
5B06
Neutral Time Overcurrent 1 Reset
5B07
Neutral Time Overcurrent 1 Block
5B08
Neutral Time Overcurrent 1 Target
5B09
Neutral Time Overcurrent 1 Events
5B0A
Reserved (6 items)
5B10
...Repeated for Neutral Time Overcurrent 2
5B20
...Repeated for Neutral Time Overcurrent 3
5B30
...Repeated for Neutral Time Overcurrent 4
B-26
RANGE
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 65535
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1
0 to 30
0 to 16
0 to 600
0 to 1
0 to 65535
0 to 2
0 to 1
0 to 1
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F102
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F300
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
---
1
F122
pu
0.001
F001
---
1
F103
0 (IEEE Mod Inv)
---
0.01
F001
---
1
F104
0 (Instantaneous)
---
1
F300
---
1
F109
---
1
F102
---
1
F001
DEFAULT
0 (SRC 1)
0 (Phasor)
1000
100
0 (Disabled)
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
0 (Phasor)
1000
100
0
0 (Self-reset)
0 (Disabled)