APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 51)
ADDR
REGISTER NAME
4718
Reserved
4719
...Repeated for breaker 2
Synchrocheck (Read/Write Setting) (2 modules)
47A0
Synchrocheck 1 Function
47A1
Synchrocheck 1 V1 Source
47A2
Synchrocheck 1 V2 Source
47A3
Synchrocheck 1 Maximum Voltage Difference
47A5
Synchrocheck 1 Maximum Angle Difference
47A6
Synchrocheck 1 Maximum Frequency Difference
47A7
Synchrocheck 1 Dead Source Select
47A8
Synchrocheck 1 Dead V1 Maximum Voltage
47A9
Synchrocheck 1 Dead V2 Maximum Voltage
47AA
Synchrocheck 1 Live V1 Minimum Voltage
47AB
Synchrocheck 1 Live V2 Minimum Voltage
47AC
Synchrocheck 1 Target
47AD
Synchrocheck 1 Events
47AE
Synchrocheck 1 Block
47AF
Synchrocheck 1 Frequency Hysteresis
47B0
...Repeated for Synchrocheck 2
Flexcurves A and B (Read/Write Settings)
4800
FlexCurve A (120 items)
48F0
FlexCurve B (120 items)
Modbus User Map (Read/Write Setting)
4A00
Modbus Address Settings for User Map (256 items)
User Displays Settings (Read/Write Setting) (16 modules)
4C00
User-Definable Display 1 Top Line Text
4C0A
User-Definable Display 1 Bottom Line Text
4C14
Modbus Addresses of Display 1 Items (5 items)
4C19
Reserved (7 items)
4C20
...Repeated for User-Definable Display 2
4C40
...Repeated for User-Definable Display 3
4C60
...Repeated for User-Definable Display 4
4C80
...Repeated for User-Definable Display 5
4CA0
...Repeated for User-Definable Display 6
4CC0
...Repeated for User-Definable Display 7
4CE0
...Repeated for User-Definable Display 8
4D00
...Repeated for User-Definable Display 9
4D20
...Repeated for User-Definable Display 10
4D40
...Repeated for User-Definable Display 11
4D60
...Repeated for User-Definable Display 12
4D80
...Repeated for User-Definable Display 13
4DA0
...Repeated for User-Definable Display 14
4DC0
...Repeated for User-Definable Display 15
4DE0
...Repeated for User-Definable Display 16
User Programmable Pushbuttons (Read/Write Setting) (12 modules)
4E00
User Programmable Pushbutton 1 Function
4E01
User Programmable Pushbutton 1 Top Line
4E0B
User Programmable Pushbutton 1 On Text
4E15
User Programmable Pushbutton 1 Off Text
4E1F
User Programmable Pushbutton 1 Drop-Out Time
4E20
User Programmable Pushbutton 1 Target
4E21
User Programmable Pushbutton 1 Events
4E22
User Programmable Pushbutton 1 LED Operand
4E23
User Programmable Pushbutton 1 Autoreset Delay
GE Multilin
RANGE
---
0 to 1
0 to 5
0 to 5
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 65535
0 to 0.1
0 to 65535
0 to 65535
0 to 65535
---
---
0 to 65535
---
0 to 2
---
---
---
0 to 60
0 to 2
0 to 1
0 to 65535
0 to 600
D30 Line Distance Protection System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
---
---
---
1
F102
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
ms
1
F011
ms
1
F011
---
1
F001
---
---
F202
---
---
F202
---
1
F001
---
---
F001
---
1
F109
---
---
F202
---
---
F202
---
---
F202
s
0.05
F001
---
1
F109
---
1
F102
---
1
F300
s
0.05
F001
DEFAULT
---
0 (Disabled)
0 (SRC 1)
B
1 (SRC 2)
10000
30
100
1 (LV1 and DV2)
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6
0
0
0
" "
""
0
0
2 (Disabled)
(none)
(none)
(none)
0
0 (Self-reset)
0 (Disabled)
0
0
B-23