4 HUMAN INTERFACES
4.3 FACEPLATE INTERFACE
ting password has been entered via the any external communications interface three times within a 3-minute time span, the
FlexLogic™ operand will be set to
On
and the D30 will not allow settings or command access
REMOTE ACCESS DENIED
"
"
via the any external communications interface for the next five minutes.
In the event that an incorrect Command or Setting password has been entered via the any external communications inter-
face three times within a three-minute time span, the
FlexLogic™ operand will be set to "On" and
REMOTE ACCESS DENIED
the D30 will not allow Settings or Command access via the any external communications interface for the next ten minutes.
The
FlexLogic™ operand will be set to "Off" after the expiration of the ten-minute timeout.
REMOTE ACCESS DENIED
4
GE Multilin
D30 Line Distance Protection System
4-29