3 HARDWARE
The wiring for the managed Ethernet switch module is shown below.
Figure 3–43: MANAGED ETHERNET SWITCH MODULE WIRING
The 10/100Base-T and 100Base-FX ports have LED indicators to indicate the port status.
The 10/100Base-T ports have three LEDs to indicate connection speed, duplex mode, and link activity. The 100Base-FX
ports have one LED to indicate linkup and activity.
A suitable IP/gateway and subnet mask must be assigned to both the switch and the UR relay for correct operation. The
Switch has been shipped with a default IP address of 192.168.1.2 and a subnet mask of 255.255.255.0. Consult your net-
work administrator to determine if the default IP address, subnet mask or default gateway needs to be modified.
Do not connect to network while configuring the switch module.
CAUTION
GE Multilin
MM fiber optic cable
MM fiber optic cable
MM fiber optic cable
MM fiber optic cable
100Base-T cable
100Base-T cable
+
110 to 250 V DC
100 to 240 V AC
Connection speed indicator (OFF = 10 Mbps; ON = 100 Mbps)
Link indicator (ON = link active; FLASHING = activity)
Duplex mode indicator (OFF = half-duplex; ON = full-duplex)
Link indicator (ON = link active; FLASHING = activity)
Figure 3–44: ETHERNET SWITCH LED INDICATORS

3.4.4 CONFIGURING THE MANAGED ETHERNET SWITCH MODULE

C70 Capacitor Bank Protection and Control System
3.4 MANAGED ETHERNET SWITCH MODULES
Tx1
100Base-FX
Rx1
Tx2
100Base-FX
Fiber
Rx2
ports
Tx1
100Base-FX
Rx1
Tx1
100Base-FX
Rx1
10/100Base-T
Copper
ports
10/100Base-T
+
W1a
W2b
Power supply
W1a
GROUND
842835A1.CDR

3.4.3 MANAGED SWITCH LED INDICATORS

842868A2.CDR