Non-Volatile Latches - GE UR Series C70 Instruction Manual

Capacitor bank protection and control system
Table of Contents

Advertisement

5.5 FLEXLOGIC™
PATH: SETTINGS
FLEXLOGIC
LATCH 1
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
5
LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
LATCH N
LATCH N
LATCH N
TYPE
SET
RESET
Reset
ON
Dominant
OFF
ON
OFF
Set
ON
Dominant
ON
OFF
OFF
Figure 5–45: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
5-104

NON-VOLATILE LATCHES

LATCH 1
FUNCTION: Disabled
LATCH 1 TYPE:
MESSAGE
Reset Dominant
LATCH 1 SET:
MESSAGE
Off
LATCH 1 RESET:
MESSAGE
Off
LATCH 1
MESSAGE
TARGET: Self-reset
LATCH 1
MESSAGE
EVENTS: Disabled
LATCH N
LATCH N
ON
OFF
OFF
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Previous
Previous
State
State
ON
OFF
ON
C70 Capacitor Bank Protection and Control System
5.5.8 NON-VOLATILE LATCHES
LATCH 1(16)
Range: Disabled, Enabled
Range: Reset Dominant, Set Dominant
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
SETTING
LATCH 1 FUNCTION:
LATCH 1 TYPE:
Disabled=0
Enabled=1
RUN
SETTING
LATCH 1 SET:
Off=0
SET
SETTING
LATCH 1 SET:
Off=0
RESET
5 SETTINGS
FLEXLOGIC OPERANDS
LATCH 1 ON
LATCH 1 OFF
842005A1.CDR
GE Multilin

Advertisement

Table of Contents
loading