GE UR Series C70 Instruction Manual page 133

Capacitor bank protection and control system
Table of Contents

Advertisement

5 SETTINGS
ACCESS REM SETG OFF: Asserted when remote setting access is disabled.
ACCESS REM SETG ON: Asserted when remote setting access is enabled.
ACCESS REM CMND OFF: Asserted when remote command access is disabled.
ACCESS REM CMND ON: Asserted when remote command access is enabled.
The appropriate events are also logged in the Event Recorder as well. The FlexLogic™ operands and events are updated
every five seconds.
A command or setting write operation is required to update the state of all the remote and local security operands
shown above.
NOTE
b) LOCAL PASSWORDS
PATH: SETTINGS
PRODUCT SETUP
CHANGE LOCAL
PASSWORDS
MESSAGE
MESSAGE
MESSAGE
Proper password codes are required to enable each access level. A password consists of 1 to 10 numerical characters.
When a
CHANGE COMMAND PASSWORD
interface, the following message sequence is invoked:
1.
ENTER NEW PASSWORD: ____________.
2.
VERIFY NEW PASSWORD: ____________.
3.
NEW PASSWORD HAS BEEN STORED.
To gain write access to a "Restricted" setting, program the
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access will be allowed. Accessibility automatically reverts to the "Restricted" level according
to the access level timeout setting values.
If an entered password is lost (or forgotten), consult the factory with the corresponding
If the setting and command passwords are identical, then this one password allows access to both com-
mands and settings.
NOTE
c) REMOTE PASSWORDS
The remote password settings are only visible from a remote connection via the EnerVista UR Setup software. Select the
Settings > Product Setup > Password Security menu item to open the remote password settings window.
Proper passwords are required to enable each command or setting level access. A command or setting password consists
of 1 to 10 numerical characters and are initially programmed to "0". The following procedure describes how the set the com-
mand or setting password.
GE Multilin
SECURITY
CHANGE LOCAL PASSWORDS
CHANGE COMMAND
PASSWORD: No
CHANGE SETTING
PASSWORD: No
ENCRYPTED COMMAND
PASSWORD: ----------
ENCRYPTED SETTING
PASSWORD: ----------
or
CHANGE SETTING PASSWORD
ACCESS LEVEL
Figure 5–2: REMOTE PASSWORD SETTINGS WINDOW
C70 Capacitor Bank Protection and Control System
5.2 PRODUCT SETUP
Range: No, Yes
Range: No, Yes
Range: 0 to 9999999999
Note: ---------- indicates no password
Range: 0 to 9999999999
Note: ---------- indicates no password
setting is programmed to "Yes" via the front panel
setting in the main security menu to "Setting" and
ENCRYPTED PASSWORD
5
.
5-9