GE UR Series C70 Instruction Manual page 509

Capacitor bank protection and control system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 34 of 53)
ADDR
REGISTER NAME
9E4C
Voltage differential 1 stage 3A pickup
9E4D
Voltage differential 1 stage 4A pickup
9E4E
Voltage differential 1 stage 1B pickup
9E5F
Voltage differential 1 stage 2B pickup
9E50
Voltage differential 1 stage 3B pickup
9E51
Voltage differential 1 stage 4B pickup
9E52
Voltage differential 1 stage 1C pickup
9E53
Voltage differential 1 stage 2C pickup
9E54
Voltage differential 1 stage 3C pickup
9E55
Voltage differential 1 stage 4C pickup
9E56
Voltage differential 1 stage 1 pickup delay
9E57
Voltage differential 1 stage 2 pickup delay
9E58
Voltage differential 1 stage 3 pickup delay
9E59
Voltage differential 1 stage 4 pickup delay
9E5A
Voltage differential 1 dropout delay
9E5B
Voltage differential 1 stage 1 block
9E5C
Voltage differential 1 stage 2 block
9E5D
Voltage differential 1 stage 3 block
9E5E
Voltage differential 1 stage 4 block
9E5F
Voltage differential 1 target
9E60
Voltage differential 1 events
9E61
...Repeated for voltage differential 2
9E82
...Repeated for voltage differential 3
VT Fuse Failure (Read/Write Setting) (6 modules)
A040
VT Fuse Failure Function
A041
...Repeated for module number 2
A042
...Repeated for module number 3
A043
...Repeated for module number 4
A044
...Repeated for module number 5
A045
...Repeated for module number 6
Selector switch actual values (read only)
A210
Selector switch 1 position
A211
Selector switch 2 position
Selector switch settings (read/write, 2 modules)
A280
Selector 1 Function
A281
Selector 1 Range
A282
Selector 1 Timeout
A283
Selector 1 Step Up
A284
Selector 1 Step Mode
A285
Selector 1 Acknowledge
A286
Selector 1 Bit0
A287
Selector 1 Bit1
A288
Selector 1 Bit2
A289
Selector 1 Bit Mode
A28A
Selector 1 Bit Acknowledge
A28B
Selector 1 Power Up Mode
A28C
Selector 1 Target
A28D
Selector 1 Events
A28E
Reserved (10 items)
A298
...Repeated for Selector 2
DNP/IEC Points (Read/Write Setting)
A300
DNP/IEC 60870-5-104 Binary Input Points (256 items)
A400
DNP/IEC 60870-5-104 Analog Input Points (256 items)
GE Multilin
RANGE
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0.001 to 1.000
0 to 600.00
0 to 600.00
0 to 600.00
0 to 600.00
0 to 600.00
0 to 65.535
0 to 65.535
0 to 65.535
0 to 65.535
0 to 2
0 to 1
0 to 1
1 to 7
1 to 7
0 to 1
1 to 7
3 to 60
0 to 65535
0 to 1
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 1
0 to 65535
0 to 2
0 to 2
0 to 1
0 to 65535
0 to 65535
C70 Capacitor Bank Protection and Control System
UNITS
STEP
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
pu
0.001
s
0.01
s
0.01
s
0.01
s
0.01
s
0.01
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
s
0.1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
---
1
---
1
---
1
B.4 MEMORY MAPPING
FORMAT
DEFAULT
F001
30
F001
40
F001
10
F001
20
F001
30
F001
40
F001
10
F001
20
F001
30
F001
40
F001
3000
F001
1000
F001
100
F001
20
F001
25
F300
0
F300
0
F300
0
F300
0
F109
0 (Self-Reset)
F102
0 (Disabled)
F102
0 (Disabled)
F001
0
F001
1
F102
0 (Disabled)
F001
7
F001
50
F300
0
F083
0 (Time-out)
F300
0
F300
0
F300
0
F300
0
F083
0 (Time-out)
F300
0
F084
0 (Restore)
F109
0 (Self-reset)
F102
0 (Disabled)
F001
0
F300
0
F300
0
B-41
B

Advertisement

Table of Contents
loading

Table of Contents