5.6 GROUPED ELEMENTS
a) MAIN MENU
PATH: SETTINGS
GROUPED ELEMENTS

NEUTRAL CURRENT

5
The C70 contains protection elements for neutral time overcurrent (ANSI device 51G), neutral instantaneous overcurrent
(ANSI device 50G), and neutral current unbalance (ANSI device 60N). A maximum of six ground time overcurrent and
twelve ground instantaneous overcurrent elements are available, dependent on the CT/VT modules ordered with the relay.
Three neutral current unbalance elements are available.
5-128
SETTING GROUP 1(6)
NEUTRAL TOC1
NEUTRAL TOC2
MESSAGE
NEUTRAL TOC6
MESSAGE
NEUTRAL IOC1
MESSAGE
NEUTRAL IOC2
MESSAGE
NEUTRAL IOC12
MESSAGE
NEUTRAL
MESSAGE
DIRECTIONAL OC1
NEUTRAL CURRENT
MESSAGE
UNBALANCE 1
NEUTRAL CURRENT
MESSAGE
UNBALANCE 2
NEUTRAL CURRENT
MESSAGE
UNBALANCE 3
C70 Capacitor Bank Protection and Control System
NEUTRAL CURRENT
See page 5–129.
See page 5–129.
See page 5–129.
See page 5–130.
See page 5–130.
See page 5–130.
See page 5–131.
See page 5–135.
See page 5–135.
See page 5–135.
5 SETTINGS
5.6.5 NEUTRAL CURRENT
GE Multilin