5.2 PRODUCT SETUP
Set
REMOTE DEVICE 1 ETYPE APPID
"0" in the example above.
Set the
REMOTE DEVICE 1 DATASET
configurable GOOSE 1 in this example, program this value as "GOOSEIn 1".
3.
Configure the data by making the following changes in the
settings menu:
Set
REMOTE IN 1 DEVICE
Set
REMOTE IN 1 ITEM
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The C70 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
For intercommunication between C70 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages. All GOOSE messages transmitted by the
C70 (DNA/UserSt dataset and configurable datasets) use the IEC 61850 GOOSE messaging services (for example, VLAN
support).
Set the
CONFIG GSE 1 FUNCTION
entered, return the
NOTE
5
PATH:...TRANSMISSION
CONFIG GSE 1
DATASET ITEMS
To create a configurable GOOSE dataset that contains an IEC 61850 Single Point Status indication and its associated qual-
ity flags, the following dataset items can be selected: "GGIO1.ST.Ind1.stVal" and "GGIO1.ST.Ind1.q". The C70 will then cre-
ate a dataset containing these two data items. The status value for GGIO1.ST.Ind1.stVal is determined by the FlexLogic™
operand assigned to GGIO1 indication 1. Changes to this operand will result in the transmission of GOOSE messages con-
taining the defined dataset.
The main reception menu is applicable to configurable GOOSE only and contains the configurable GOOSE dataset items
for reception:
PATH:...RECEPTION
CONFIG GSE 1
DATASET ITEMS
The configurable GOOSE settings allow the C70 to be configured to receive a number of different datasets within IEC
61850 GOOSE messages. Up to eight different configurable datasets can be configured for reception. This is useful for
intercommunication between C70 IEDs and devices from other manufacturers that support IEC 61850.
For intercommunication between C70 IEDs, the fixed (DNA/UserSt) dataset can be used. The DNA/UserSt dataset con-
tains the same DNA and UserSt bit pairs that are included in GSSE messages.
To set up a C70 to receive a configurable GOOSE dataset that contains two IEC 61850 single point status indications, the
following dataset items can be selected (for example, for configurable GOOSE dataset 1): "GGIO3.ST.Ind1.stVal" and
"GGIO3.ST.Ind2.stVal". The C70 will then create a dataset containing these two data items. The Boolean status values from
these data items can be utilized as remote input FlexLogic™ operands. First, the
must be set to contain dataset "GOOSEIn 1" (that is, the first configurable dataset). Then
must be set to "Dataset Item 1" and "Dataset Item 2". These remote input FlexLogic™ operands will then change state in
accordance with the status values of the data items in the configured dataset.
Floating point analog values originating from MMXU logical nodes may be included in GOOSE datasets. Deadband (non-
instantaneous) values can be transmitted. Received values are used to populate the GGIO3.XM.AnIn1 and higher items.
Received values are also available as FlexAnalog parameters (GOOSE analog In1 and up).
5-26
to match the ETHERTYPE application ID from the transmitting device. This is
value. This value represents the dataset number in use. Since we are using
to "GOOSEOut_1".
to "Dataset Item 2". This assigns the value of the GGIO3.ST.Ind1.stVal single point status
function to "Disabled" when configuration changes are required. Once changes are
to "Enabled" and restart the unit for changes to take effect.
CONFIG GSE 1 FUNCTION
CONFIGURABLE GOOSE 1(8)
ITEM 1:
GGIO1.ST.Ind1.stVal
CONFIGURABLE GOOSE 1(8)
ITEM 1:
GGIO1.ST.Ind1.stVal
C70 Capacitor Bank Protection and Control System
INPUTS/OUTPUTS
CONIFIG GSE 1(64) DATA TIMES
Range: all valid MMS data item references for
transmitted data
CONIFIG GSE 1(64) DATA ITEMS
Range: all valid MMS data item references for
transmitted data
5 SETTINGS
REMOTE INPUTS
REMOTE INPUT 1
ITEM 1(64)
REMOTE DEVICE 1(16) DATASET
REMOTE IN 1(16) ITEM
GE Multilin
setting
settings