GE UR Series C70 Instruction Manual page 482

Capacitor bank protection and control system
Table of Contents

Advertisement

B.4 MEMORY MAPPING
Table B–9: MODBUS MEMORY MAP (Sheet 7 of 53)
ADDR
REGISTER NAME
2700
IEC 61850 received uinteger 9
2702
IEC 61850 received uinteger 10
2704
IEC 61850 received uinteger 11
2706
IEC 61850 received uinteger 12
2708
IEC 61850 received uinteger 13
B
270A
IEC 61850 received uinteger 14
270C
IEC 61850 received uinteger 15
270E
IEC 61850 received uinteger 16
Source Current THD And Harmonics (Read Only) (6 modules)
2800
Ia THD for Source 1
2801
Ia Harmonics for Source 1 - 2nd to 25th (24 items)
2821
Ib THD for Source 1
2822
Ib Harmonics for Source 1 - 2nd to 25th (24 items)
283A
Reserved (8 items)
2842
Ic THD for Source 1
2843
Ic Harmonics for Source 1 - 2nd to 25th (24 items)
285B
Reserved (8 items)
2863
...Repeated for Source 2
28C6
...Repeated for Source 3
2929
...Repeated for Source 4
298C
...Repeated for Source 5
29EF
...Repeated for Source 6
Expanded FlexStates (Read Only)
2B00
FlexStates, one per register (256 items)
Expanded Digital Input/Output states (Read Only)
2D00
Contact Input States, one per register (96 items)
2D80
Contact Output States, one per register (64 items)
2E00
Virtual Output States, one per register (96 items)
Expanded Remote Input/Output Status (Read Only)
2F00
Remote Device States, one per register (16 items)
2F80
Remote Input States, one per register (64 items)
Oscillography Values (Read Only)
3000
Oscillography Number of Triggers
3001
Oscillography Available Records
3002
Oscillography Last Cleared Date
3004
Oscillography Number Of Cycles Per Record
Oscillography Commands (Read/Write Command)
3005
Oscillography Force Trigger
3011
Oscillography Clear Data
User Programmable Fault Report Commands (Read/Write Command)
3060
User Fault Report Clear
User Programmable Fault Report Actuals (Read Only)
3070
Newest Record Number
3071
Cleared Date
3073
Report Date (10 items)
User Programmable Fault Report (Read/Write Setting) (2 modules)
3090
Fault Report 1 Fault Trigger
3091
Fault Report 1 Function
3092
Fault Report 1 Prefault Trigger
3093
Fault Report Analog Channel 1 (32 items)
30B3
Fault Report 1 Reserved (5 items)
30B8
...Repeated for Fault Report 2
Modbus file transfer (read/write)
3100
Name of file to read
B-14
RANGE
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 4294967295
0 to 99.9
0 to 99.9
0 to 99.9
0 to 99.9
0 to 0.1
0 to 99.9
0 to 99.9
0 to 0.1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 65535
0 to 400000000
0 to 65535
0 to 1
0 to 1
0 to 1
0 to 65535
0 to 4294967295
0 to 4294967295
0 to 65535
0 to 1
0 to 65535
0 to 65536
C70 Capacitor Bank Protection and Control System
UNITS
STEP
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
0.1
---
0.1
---
0.1
---
0.1
---
0.1
---
0.1
---
0.1
---
0.1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
1
---
---
---
---
---
---
APPENDIX B
FORMAT
DEFAULT
F003
0
F003
0
F003
0
F003
0
F003
0
F003
0
F003
0
F003
0
F001
0
F001
0
F001
0
F001
0
F001
0
F001
0
F001
0
F001
0
F108
0 (Off)
F108
0 (Off)
F108
0 (Off)
F108
0 (Off)
F155
0 (Offline)
F108
0 (Off)
F001
0
F001
0
F050
0
F001
0
F126
0 (No)
F126
0 (No)
F126
0 (No)
F001
0
F050
0
F050
0
F300
0
F102
0 (Disabled)
F300
0
F600
0
F001
0
F204
(none)
GE Multilin

Advertisement

Table of Contents
loading