GE UR Series C70 Instruction Manual page 146

Capacitor bank protection and control system
Table of Contents

Advertisement

5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
TRANSMISSION
The general transmission settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
GENERAL
The
DEFAULT GSSE/GOOSE UPDATE TIME
put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. This
setting controls the steady-state heartbeat time interval.
The
DEFAULT GSSE/GOOSE UPDATE TIME
The GSSE settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
5
GSSE
These settings are applicable to GSSE only. If the fixed GOOSE function is enabled, GSSE messages are not transmitted.
The
setting represents the IEC 61850 GSSE application ID name string sent as part of each GSSE message. This
GSSE ID
string identifies the GSSE message to the receiving device. In C70 releases previous to 5.0x, this name string was repre-
sented by the
RELAY NAME
The fixed GOOSE settings are shown below:
PATH: SETTINGS
PRODUCT...
FIXED GOOSE
5-22
COMMUNICATIONS
GENERAL
GSSE
MESSAGE
FIXED GOOSE
MESSAGE
CONFIGURABLE
MESSAGE
GOOSE
COMMUNICATIONS
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
sets the time between GSSE or GOOSE messages when there are no remote out-
setting is applicable to GSSE, fixed C70 GOOSE, and configurable GOOSE.
COMMUNICATIONS
GSSE FUNCTION:
Enabled
GSSE ID:
MESSAGE
GSSEOut
DESTINATION MAC:
MESSAGE
000000000000
setting.
COMMUNICATIONS
GOOSE FUNCTION:
Disabled
GOOSE ID:
MESSAGE
GOOSEOut
DESTINATION MAC:
MESSAGE
000000000000
GOOSE VLAN PRIORITY:
MESSAGE
4
GOOSE VLAN ID:
MESSAGE
0
GOOSE ETYPE APPID:
MESSAGE
0
C70 Capacitor Bank Protection and Control System
IEC 61850 PROTOCOL
GSSE/GOOSE...
IEC 61850...
GSSE/GOOSE...
Range: 1 to 60 s in steps of 1
IEC 61850...
GSSE/GOOSE...
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
IEC 61850...
GSSE/GOOSE...
Range: Enabled, Disabled
Range: 65-character ASCII string
Range: standard MAC address
Range: 0 to 7 in steps of 1
Range: 0 to 4095 in steps of 1
Range: 0 to 16383 in steps of 1