Capacitor Control - GE UR Series C70 Instruction Manual

Capacitor bank protection and control system
Table of Contents

Advertisement

6.3 METERING
i) VOLTAGE HARMONICS AND THD METERING
PATH: ACTUAL VALUES
VOLTAGE HARMONICS
SRC 1
The metered current harmonics values are displayed in this menu. The "SRC 1" text will be replaced by the programmed
name for the associated source (see the
To extract the 2nd to 25th voltage harmonics, each harmonic is computed on a per-phase basis, where:
N = 64 is the number of samples per cycle
ω
= 2πf is the angular frequency based on the system frequency (50 or 60 Hz)
0
k = 1, 2,..., N – 1 is the index over one cycle for the Fast Fourier Transform (FFT)
m is the last sample number for the sliding window
h = 1, 2,..., 25 is the harmonic number
The short-time Fourier transform is applied to the unfiltered signal:
6
The harmonics are a percentage of the fundamental signal obtained as a ratio of harmonic amplitude to fundamental ampli-
tude multiplied by 100%. The total harmonic distortion (THD) is the ratio of the total harmonic content to the fundamental:
Voltage harmonics are calculated only for Wye connected phase VTs. Ensure the
VOLTAGE BANK F5
NOTE
PATH: ACTUAL VALUES

CAPACITOR CONTROL

These values indicate the time remaining before the next permissible close operation for each of the four capacitor banks.
6-16
METERING
SOURCE SRC 1
SRC 1
THD Va:
Vb:
0.0 Vc:
SRC 1
2ND Va:
MESSAGE
Vb:
0.0 Vc:
SRC 1
3RD Va:
MESSAGE
Vb:
0.0 Vc:
SRC 1
25TH Va:
MESSAGE
Vb:
0.0 Vc:
SETTINGS
2
(
,
)
--- -
F
m h
=
real
N
k
2
(
m h ,
)
--- -
F
=
imag
N
k
(
m h ,
)
F
F
=
ampl
real
THD
=
PHASE VT XX CONNECTION
METERING
CAPACITOR CONTROL
CAP 1 DISCHARGE TIME:
0 s
CAP 2 DISCHARGE TIME:
MESSAGE
0 s
CAP 3 DISCHARGE TIME:
MESSAGE
0 s
CAP 4 DISCHARGE TIME:
MESSAGE
0 s
C70 Capacitor Bank Protection and Control System
VOLTAGE HARMONICS
0.0
0.0%
0.0
0.0%
0.0
0.0%
0.0
0.0%
SYSTEM SETUP
SIGNAL SOURCES
(
(
)
(
h ω
t k ( )
)
)
f m k
cos
0
(
(
)
(
h ω
t k ( )
)
)
f m k
sin
0
2
2
(
,
)
(
,
)
m h
F
m h
+
imag
2
2
2
...
F
+
F
+
+
F
2
3
25
setting is "Wye" to enable voltage harmonics metering.
6 ACTUAL VALUES
menu).
(EQ 6.1)
(EQ 6.2)
SYSTEM SETUP
AC INPUTS
6.3.3 CAPACITOR CONTROL
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents