GE UR Series C70 Instruction Manual page 497

Capacitor bank protection and control system
Table of Contents

Advertisement

APPENDIX B
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 53)
ADDR
REGISTER NAME
6324
Bank phase overvoltage 1 curve
6325
Bank phase overvoltage 1 curve time multiplier
6326
Bank phase overvoltage 1 stage 1A pickup
6327
Bank phase overvoltage 1 stage 2A pickup
6328
Bank phase overvoltage 1 stage 3A pickup
6329
Bank phase overvoltage 1 stage 4A pickup
632A
Bank phase overvoltage 1 stage 1B pickup
632B
Bank phase overvoltage 1 stage 2B pickup
632C
Bank phase overvoltage 1 stage 3B pickup
632D
Bank phase overvoltage 1 stage 4B pickup
632E
Bank phase overvoltage 1 stage 1C pickup
632F
Bank phase overvoltage 1 stage 2C pickup
6330
Bank phase overvoltage 1 stage 3C pickup
6331
Bank phase overvoltage 1 stage 4C pickup
6332
Bank phase overvoltage 1 stage 1 pickup delay
6333
Bank phase overvoltage 1 stage 2 pickup delay
6334
Bank phase overvoltage 1 stage 3 pickup delay
6335
Bank phase overvoltage 1 dropout delay
6336
Bank phase overvoltage 1 block
6337
Bank phase overvoltage 1 target
6338
Bank phase overvoltage 1 events
6339
...Repeated for bank phase overvoltage 2
6352
...Repeated for bank phase overvoltage 3
Capacitor bank overvoltage actual values (read only, 3 modules)
636B
Bank overvoltage 1 phase A operate voltage
636C
Bank overvoltage 1 phase B operate voltage
636D
Bank overvoltage 1 phase C operate voltage
636E
...Repeated for bank phase overvoltage 2
6371
...Repeated for bank phase overvoltage 3
Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)
6400
Negative Sequence Instantaneous OC 1 Function
6401
Negative Sequence Instantaneous OC 1 Signal Source
6402
Negative Sequence Instantaneous Overcurrent 1 Pickup
6403
Negative Sequence Instantaneous Overcurrent 1 Delay
6404
Negative Sequence Instantaneous OC 1 Reset Delay
6405
Negative Sequence Instantaneous Overcurrent 1 Block
6406
Negative Sequence Instantaneous Overcurrent 1 Target
6407
Negative Sequence Instantaneous Overcurrent 1 Events
6408
Reserved (8 items)
6410
...Repeated for Negative Sequence Instantaneous OC 2
Negative Sequence Overvoltage (Read/Write Grouped Setting)
64A0
Negative Sequence Overvoltage Function
64A1
Negative Sequence Overvoltage Source
64A2
Negative Sequence Overvoltage Pickup
64A3
Negative Sequence Overvoltage Pickup Delay
64A4
Negative Sequence Overvoltage Reset Delay
64A5
Negative Sequence Overvoltage Block
64A6
Negative Sequence Overvoltage Target
64A7
Negative Sequence Overvoltage Events
Time of day timer settings (read/write, grouped, 5 modules)
6570
Time of day timer 1 function
6571
Time of day timer 1 start time
6573
Time of day timer 1 stop time
6575
Time of day timer 1 targets
GE Multilin
RANGE
0 to 3
1.00 to 10.00
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0.800 to 2.000
0 to 600.00
0 to 600.00
0 to 600.00
0 to 600.00
0 to 65535
0 to 2
0 to 1
0 to 65.535
0 to 65.535
0 to 65.535
0 to 1
0 to 5
0 to 30
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 1
0 to 5
0 to 1.25
0 to 600
0 to 600
0 to 65535
0 to 2
0 to 1
0 to 1
0 to 2359
0 to 2359
0 to 2
C70 Capacitor Bank Protection and Control System
B.4 MEMORY MAPPING
UNITS
STEP
FORMAT
---
1
F094
---
0.01
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
pu
0.001
F001
pu
0.001
F001
pu
0.001
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F001
---
1
F102
---
1
F167
pu
0.001
F001
s
0.01
F001
s
0.01
F001
---
1
F300
---
1
F109
---
1
F102
---
1
F102
---
1
F050
---
1
F001
---
1
F109
DEFAULT
0 (FlexCurve A)
100
1050
1100
1200
B
1050
1050
1100
1200
1050
1050
1100
1200
1050
6000
1000
200
25
0
0 (Self-reset)
0 (Disabled)
0
0
0
0 (Disabled)
0 (SRC 1)
1000
0
0
0
0 (Self-reset)
0 (Disabled)
0
0 (Disabled)
0 (SRC 1)
300
50
50
0
0 (Self-reset)
0 (Disabled)
0 (Disabled)
0
2359
0 (Self-reset)
B-29