Suppres; Supv; Util; Trouble - Simplex 4010 Applications Manual

Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Point Types,

SUPPRES

SUPV

UTIL

TROUBLE

VSMOKE

Technical Manuals Online! - http://www.tech-man.com
Continued
Suppression agent pressure switch monitor.
Circuit Status
Normal
Limited
Open
Short
Used to monitor any supervisory type device where operator acknowledgment is
required.
Circuit Status
Normal
Limited
Open
Short
Used to monitor and supervise any condition; operator acknowledgment is not
required. No alarm is generated by this point type.
Circuit Status
Normal
Limited
Open
Short
Used for trouble monitoring only. No alarm is generated by this point type.
Circuit Status
Normal
Limited
Open
Short
Used with smoke detectors whose alarm status must be verified.
Circuit Status
Normal
Limited
Open
Short
LCD Text
Suppression Pressure
Suppression Pressure
Suppression Pressure
LCD Text
Supervisory Monitor
Supervisory Monitor
Supervisory Monitor
LCD Text
Utility Monitor
Utility Monitor
Utility Monitor
LCD Text
Trouble Monitor
Trouble Monitor
Trouble Monitor
LCD Text
Smoke Detector
Smoke Detector
Smoke Detector
A-15
Status
Normal
Discharge
Open Trouble
Short Trouble
Status
Normal
Abnormal
Open Trouble
Abnormal
Status
Normal
Abnormal
Open Trouble
Abnormal
Status
Normal
Abnormal
Open Trouble
Abnormal
Status
Normal
Verified Alarm
Open Trouble
Fire Alarm
Continued on next page

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents