Wso; Supdet; Supabrt; Supdump - Simplex 4010 Applications Manual

Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Point Types,
SO

WSO

SUPDET

SUPABRT

SUPDUMP

Technical Manuals Online! - http://www.tech-man.com
Continued
Used to indicate abnormal sprinkler conditions, such as the opening of a PIV or
OS&Y tamper switch. This point type must be used with normally open
contacts only.
Circuit Status
Normal
Limited
Open
Short
Combination Waterflow/Sprinkler Monitor (NO). Where permitted by the AHJ,
this circuit operates both waterflow monitors and PIV/OS&Y tampers on the
same circuit. All tamper switches (N.O. contacts) must be connected with a
current limiting resistor. Refer to the 4010 field wiring diagrams. A short
condition indicates waterflow alarms.
Circuit Status
Normal
Limited
Open
Short
Suppression (Agent Discharge) Monitor.
Circuit Status
Normal
Limited
Open
Short
Suppression Abort (supervised)
Circuit Status
Normal
Limited
Open
Short
Manual suppression agent discharge
Circuit Status
Normal
Limited
Open
Short
LCD Text
Normal
Sprinkler Monitor
Sprinkler Monitor
Sprinkler Monitor
LCD Text
Sprinkler Monitor
Sprinkler Monitor
Sprinkler Monitor
LCD Text
Suppression Detector
Suppression Detector
Suppression Detector
LCD Text
Suppression Abort
Suppression Abort
Suppression Abort
LCD Text
Suppression Manual Dump
Suppression Manual Dump
Suppression Manual Dump
A-14
Status
Abnormal
Open Trouble
Abnormal
Status
Normal
Abnormal
Open Trouble
Waterflow Alarm
Status
Normal
Fire Alarm
Open Trouble
Fire Alarm
Status
Normal
Activated
Open Trouble
Short Trouble
Status
Normal
Activated
Open Trouble
Short Trouble
Continued on next page