QuickAlert Class A / Class B Guidelines,
Class B QuickAlert
Technical Manuals Online! - http://www.tech-man.com
Continued
Class B QuickAlert with SmartSync operation depends on the following factors:
•
All strobes must be Simplex synchronized VO, not free run. All
A/V's, must be QuickAlert SmartSync compatible. Other
manufacturer's appliances are not compatible on a QuickAlert
SmartSync two-wire circuit.
•
The QuickAlert with SmartSync notification appliance circuits connect
directly to the 4010 notification appliance circuits terminals. The
4905-9938 SmartSync Control Module is not required.
•
For General Alarm operation, the point type SQALERT must be
utilized, which will provide the QuickAlert Horns to be controlled "Off
on Silence" and the Visuals to be controlled "Off on Reset." For any
selective signal operation, the point type QALERT (no default
operation) must be utilized and all operations must programmed in
Custom Control.
•
QuickAlert Horn operation (Slow March Time, Steady or Temporal) is
selected in the System Options, Signal Operation, under QuickAlert
Horn.