Dholder; Primary; Qalert; Sqalert - Simplex 4010 Applications Manual

Hide thumbs Also See for 4010:
Table of Contents

Advertisement

Point Types,

DHOLDER

PRIMARY

QALERT

SQALERT

RELAY

Technical Manuals Online! - http://www.tech-man.com
Continued
Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm (any point in L1 General Alarm
List goes into alarm), loss of AC Power, or when programmed.
Circuit Status
ON
OFF
Disable TBL
OFF AUTO TBL
Elevator capture – primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. A relay assigned this point
type turns ON when any point in L4, Primary Elevator Recall, goes into alarm.
Relay turns Off on reset.
Circuit Status
ON
OFF
Disable TBL
OFF AUTO TBL
QuickAlert signal. QALERT device type has no automatic operation. All
operations for this type of device type must be programmed with Custom
Control.
SQALERT device type automatically turns on the designated circuit on alarm
detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.
Generic relay – no default operation. Used for selective relay applications
(Custom Control) not defined by a specific point type. Point must be
programmed to turn ON and OFF.
Circuit Status
ON
OFF
Disable TBL
OFF AUTO TBL
LCD Display
Door Holder
Door Holder
Door Holder
Door Holder
Door Holder
LCD Display
Pri Elevator Capture
Pri Elevator Capture
Pri Elevator Capture
Pri Elevator Capture
Pri Elevator Capture
LCD Display
Auxiliary Relay
Auxiliary Relay
Auxiliary Relay
Auxiliary Relay
Auxiliary Relay
A-6
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
Continued on next page