Selective Activation of Single Station Devices,
Step 3. Add Custom Control
Equations (continued)
Technical Manuals Online! - http://www.tech-man.com
Equation 1. This equation uses a single input qualifier to monitor List L26,
which contains all of Floor 1's pull stations. If any pull station within this list
activates, this equation's output qualifiers execute. The first output qualifier
programs the tone used by the single station sounders when they activate. The
second output qualifier turns on the sounders in the area of the activated pull
station.
Note: You cannot put single station devices in a list; each device must be
separately listed in the Custom Control program, as shown in Figure 2-11.
Equation 2. The input qualifier used in this equation monitors the state of P26,
which is ON if an Alarm Silence has been performed. The output qualifiers
only execute when P26 is ON (i.e., following Alarm Silence). The first output
qualifier, Device Code OFF, turns off the sounders on the single station devices.
The second output qualifier resets the state of P26.
Note: Resetting P26 is very important. Do not leave this step out.
Equation 1
Equation 2
Figure 2-11. Selective Activation of Single Station Devices
Continued