Point Types,

RSIGNAL

RVISUAL

RWATER

Technical Manuals Online! - http://www.tech-man.com
Continued
Alarm signal – On until Reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
Circuit Status
ON
OFF
Disable TBL
OFF AUTO TBLE
Used only with visual notification appliances that must be ON until a System
Reset is performed. Points assigned with this type operate on general alarm
(that is, when any point within the L1 General Alarm List goes into alarm).
Circuit Status
ON
OFF
Disable TBL
Off Auto TBL
Waterflow signal – On until Reset. A point with this type turns ON when any
point within L2, the Waterflow Alarm Monitor List, goes into alarm. Points
with this type turn OFF on System Reset.
Circuit Status
ON
OFF
Disable TBL
Off Auto TBL
LCD Display
Signal Circuit
Signal Circuit
Signal Circuit
Signal Circuit
Signal Circuit
LCD Display
Visual
Visual
Visual
Visual
Visual
LCD Display
Signal Circuit
Signal Circuit
Signal Circuit
Signal Circuit
Visual
A-7
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
System Status
ON
OFF
CODING
TROUBLE
TROUBLE
Continued on next page