Selective Signaling by Fire Floor, Floor Above, and Floor Below

Overview

Step 1. Define NAC's Device
Types / Point Types / Custom
Label
Technical Manuals Online! - http://www.tech-man.com
This application limits the activation of NACs to the floor on which the
activated initiating device is located, referred to as the fire floor, and the floors
immediately above and below the fire floor.
In the figure above, an activated smoke detector or pull station on Floor 3
activates the NACs on Floors 2, 3, and 4.
The NACs used with this application can be either the NACs located on the
panel's SFIO board or the NACs located on a 4009 IDNet NAC extender.
Use the PC Programmer to program the NACs with the following device types
and point types. When defining custom labels, make sure to use descriptive
labels, such as "FLOOR-1 AUDIBLE NACS."
For QuickAlert applications, refer to "QuickAlert Class A / Class B Guidelines"
in Chapter 1.