Dual Detector, Pre-Signal, and Abort Switch with No Delay,
Programming System
Options, Point Types, and
Lists (continued)

Programming Custom Control

Technical Manuals Online! - http://www.tech-man.com
3.
Use the PC Programmer's list tab to add the initiating devices and output
points to the appropriate lists, as follows:
List
L9
Automatic Suppression Release Points. Add all automatic
initiating devices whose activation should result in the release
of the suppression agent.
L10
Suppression Manual Release Points. Add all manual
suppression release points whose activation should result in
the release of the suppression agent.
L11
Suppression Release Abort Points. Add all abort switch
points to this list.
L12
Suppression Release Output Points. Add the NACs that
control the suppression release solenoids.
The following example, shown in Figure 3-4, illustrates how to implement this
application.
Equation 1. The input side of this equation monitors the FIRE state of list
L9, which is a system list containing all suppression-related automatic
initiating devices. The output side of Equation 1 programs the NAC
appliances to sound in SLOW MARCH TIME when any point within list
L9 enters an ALARM condition.
Equation 2. The input side of Equation 2 monitors L9 (suppression-
related automatic initiating devices) and L10 (suppression-related manual
release points). If there is an activated device in either list, the output side
of the equation executes, activating the NAC appliances in FAST MARCH
TIME.
Equation 3. The input side of Equation 3 monitors the suppression release
output points contained in system list L12. If any of the points in this list
are ON/CODING, the NACs are held ON, indicating that the suppression
agent has been released.
Figure 3-4. Custom Control for Pre-Signal
3-7
Continued
Add These Points