AUMA SG 05.1 Operation Instructions Manual page 44

Control unit: electronic (mwg) with actuator controls aumatic ac 01.1 non-intrusive
Table of Contents

Advertisement

Commissioning (basic settings)
44
SG 05.1
SG 12.1/SGR 05.1
Default value: according to order data
Setting range: according to torque setting range, refer to actuator name plate
Step by step:
1.
Set selector switch to position 0 (OFF).
2.
Press
and hold it down for approx. 3 seconds.
C
Display indicates:
MAIN MENU
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3.
Press .
Display indicates:
MAIN MENU
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4.
Press
.
Display indicates:
SETTINGS
SET LIMIT SWITCHES
SEATING MODE
TORQUE
5.
Press
twice.
Display indicates:
SETTINGS
SET LIMIT SWITCHES
SEATING MODE
TORQUE
6.
Press
.
Display indicates:
TORQUE
VIEW
EDIT
Use
and
to select between
SGR 12.1 Control unit: electronic (MWG)
AC 01.1 Non-Intrusive Modbus RTU
M0
M1
M10
M12
M120
VIEW
and
EDIT
.