GE N60 Instruction Manual page 501

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
— This setting selects the FlexAnalog parameter used to drive the associated direct analog output.
ANALOG 1 VALUE
— This setting specifies the deadband value used to trigger transmission of the associated direct
ANALOG 1 DEADBAND
analog output. This value is stored as an IEEE 754 / IEC 60559 floating-point number. Because of the large range for this
setting, not all values can be stored—some values can be rounded to the closest possible floating point number.
— This setting selects the FlexLogic operand used to trigger the transmission of the associated direct
ANALOG 1 TRIGGER
analog output. Transmission occurs on the rising edge of the operand. The operand must transition from 0 to 1 and remain
at a value of 1 for at least one power system cycle to ensure detection of the rising edge and transmission of the
associated direct analog output.
5.9.7.3 Direct analog inputs
SETTINGS  INPUTS/OUTPUTS  DIRECT ANALOGS  DIRECT ANALOG INPUTS  DIRECT ANALOG 1(32) INPUT
 DIRECT ANALOG 1
 INPUT
The direct analogs feature allows the transmission of analog values between any two UR-series relays supporting the
feature. The communication channel is the same as that used for the direct inputs and outputs feature. When the direct
inputs/outputs and direct analog features are used together on the same channel, the UR-series relays must be using
firmware version 5.20 or higher.
The settings for direct analog input 1 are as follows. The description applies to all 32 direct analog inputs.
— This value selects the source of the direct analog 1 input. Direct analog input 1 is driven by
DIRECT ANALOG 1 DEVICE ID
the device programmed in this setting.
— This value specifies which input to extract the value for the direct analog 1 input. Direct analog
DIRECT ANALOG 1 NUMBER
input 1 is driven by the input programmed in this setting. This setting value corresponds to the direct analog output
number of the sending device.
— This setting specifies the value of direct analog input 1 when the associated direct device is
DIRECT ANALOG 1 DEFAULT
offline and the
DIRECT ANALOG 1 DEFAULT MODE
the default mode is set to "Last Known," the value of direct analog input 1 remains at the last received value. This value is
stored as an IEEE 754 / IEC 60559 floating-point number. Because of the large range for this setting, not all values can be
stored—some values can be rounded to the closest possible floating point number.
— This setting provides a four-character string that is used in the direct analog input 1 actual
DIRECT ANALOG 1 UNITS
values display.
— This setting defines the per-unit base factor when using the
DIRECT ANALOG 1 PU
FlexAnalog value in other N60 features, such as FlexElements. This value is used to normalize the direct analog input 1
FlexAnalog quantity to its per-unit base. See the FlexElements section for additional details on per-unit base values.
5.9.7.4 Application example
Direct analog input FlexAnalog parameters (the
other N60 functions that use FlexAnalog parameters.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
DIRECT ANALOG 1
DEVICE: 0
DIRECT ANALOG 1
NUMBER: 0
ANALOG 1 DEFAULT:
1000.000
ANALOG 1 DEFAULT
MODE: Default Value
DIRECT ANALOG 1
UNITS: unit
DIRECT ANALOG 1PU:
1
is set to "Default Value." When the associated direct device is offline and
DIR ANALOG INPUT 1
Range: 0 to 16 in steps of 1
Range: 0 to 32 in steps of 1
Range: –1000000000.000 to 1000000000.000 in
steps of 0.001
Range: Default Value, Last Known
Range: up to four alphanumeric characters
Range: 1 to 2000000 in steps of 1
DIRECT ANALOG INPUT 1 ACTUAL
to
values) are available for use in
DIR ANALOG INPUT 32
INPUTS/OUTPUTS
5
5-307