Product Setup; Security - GE N60 Instruction Manual

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP

5.3 Product setup

5.3.1 Security

5.3.1.1 Security overview
The following security features are available:
Password security — Basic security present by default
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The
feature is present by default in the EnerVista software.
CyberSentry security — Advanced security available using a software option. When purchased, the option is
automatically enabled, and the default Password security and EnerVista security are disabled.
Lost password
If all passwords are lost, recovery is possible by resetting the unit to default values. Note that the relay is reset to default
values, not just the passwords.
To reset the unit after a lost password:
1.
Email GE customer service at multilin.tech@ge.com with the serial number and using a recognizable corporate email
account. Customer service provides a code to reset the relay to the factory defaults.
2.
Enter the reset code on the front panel, under
3.
Change the default password of ChangeMe1# as outlined in the Set Up CyberSentry and Change Default Password
5
section at the end of the Installation chapter.
Password requirements
A user account requires an alpha-numeric password that meets the following requirements:
Password is case-sensitive
Password cannot contain the user account name or parts of the user account that exceed two consecutive
characters
Password must be 8 to 20 characters in length
Password must contain characters from all of the following categories:
English uppercase characters (A through Z)
English lowercase characters (a through z)
Base 10 digits (0 through 9)
Non-alphabetic characters (for example, ~, !, @, #, $,%, &)
5.3.1.2 Password security
SETTINGS  PRODUCT SETUP  SECURITY
 SECURITY
5-8

COMMANDS
ACCESS LEVEL:
Restricted
 CHANGE LOCAL
 PASSWORDS
 CHANGE REMOTE
 PASSWORDS
 ACCESS
 SUPERVISION
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
RELAY MAINTENANCE
SERVICE COMMAND
Range: Restricted, Command, Setting,
Factory Service (for factory use only)
See page 5-10
See page 5-10
See page 5-11
CHAPTER 5: SETTINGS
.

Advertisement

Table of Contents
loading

Table of Contents