GE N60 Instruction Manual page 347

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The disconnect switch control element contains the auxiliary logic for status and serves as the interface for opening and
closing of disconnect switches from SCADA or through the front panel interface. The disconnect switch control element
can be used to create interlocking functionality. For greater security in determination of the switch pole position, both the
89/a and 89/b auxiliary contacts are used with reporting of the discrepancy between them. There are eight disconnect
switch control elements for each CT/VT module installed.
To use this element, configure the contact outputs that open and close the disconnect switch to use FlexLogic operands
and
SWITCH 1 OFF CMD
SWITCH 1 ON
— This setting enables and disables operation of the disconnect switch element.
SWITCH 1 FUNCTION
— Assign a user-defined name (up to six characters) to the disconnect switch. This name is used in flash
SWITCH 1 NAME
messages related to disconnect switch 1.
— This setting selects "3-Pole" mode, where disconnect switch poles have a single common auxiliary
SWITCH 1 MODE
switch, or "1-Pole" mode where each disconnect switch pole has its own auxiliary switch.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
SWITCH 1 BLK OPEN:
Off
SWITCH 1 CLOSE:
Off
SWITCH 1 BLK CLOSE:
Off
SWTCH 1 ΦA/3P CLSD:
Off
SWTCH 1 ΦA/3P OPND:
Off
SWITCH 1 ΦB CLOSED:
Off
SWITCH 1 ΦB OPENED:
Off
SWITCH 1 ΦC CLOSED:
Off
SWITCH 1 ΦC OPENED:
Off
SWITCH1 PUSH BUTTON
CONTROL: Disabled
SWITCH 1 TAGGING:
Disabled
SWITCH 1 SUBSTITUTN:
Disabled
SWITCH 1 BYPASS:
Disabled
SWITCH 1 OPEN
SEAL-IN:
0.000 s
SWITCH 1 CLOSE
SEAL-IN:
0.000 s
SWITCH 1 TOPERATE:
70 ms
SWITCH 1 ALARM
DELAY:
0.000 s
SWITCH 1 EVENTS:
Disabled
CMD, and configure the disconnect switch control element's inputs as outlined here.
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0 to 65535 ms in steps of 1
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
SYSTEM SETUP
5
5-153