CHAPTER 5: SETTINGS

5.8.10 Monitoring elements

5.8.10.1 Menu
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS
 MONITORING
 ELEMENTS
5.8.10.2 VT fuse failure
SETTINGS  CONTROL ELEMENTS  MONITORING ELEMENTS  VT FUSE FAILURE 1(6)
 VT FUSE FAILURE 1
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Figure 5-150: Digital counter logic
 VT FUSE FAILURE 1
 VT FUSE FAILURE 6
 CT FAILURE
 DETECTOR 1
 CT FAILURE
 DETECTOR 6
 THERMAL OVERLOAD
 PROTECTION
VT FUSE FAILURE 1
FUNCTION: Disabled
VT FUSE FAILURE 1
ALARM DELAY: 1.000 s
See below
See page 5-277
See page 5-279
Range: Disabled, Enabled
Range: 0.000 to 65.535 s in steps of 0.001
CONTROL ELEMENTS
5
5-275