Flexlogic Equation Editor; Flexlogic Timers; Flexelements - GE N60 Instruction Manual

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

FLEXLOGIC
TIMER 2
= Virt Op 4
END
In this expression, the virtual output 4 input to the four-input OR is listed before it is created. This is typical of a form of
feedback, in this case, used to create a seal-in effect with the latch, and is correct.
8.
Always test the logic after it is loaded into the relay, in the same way as has been used in the past. Testing can be
simplified by placing an "END" operator within the overall set of FlexLogic equations. The equations are evaluated up
to the first "END" operator.
The "On" and "Off" operands can be placed in an equation to establish a known set of conditions for test purposes, and
the "INSERT" and "DELETE" commands can be used to modify equations.

5.6.5 FlexLogic equation editor

SETTINGS  FLEXLOGIC  FLEXLOGIC EQUATION EDITOR
 FLEXLOGIC
 EQUATION EDITOR
There are 1,024 FlexLogic entries available, numbered from 1 to 1024, with default END entry settings. If a "Disabled"
element is selected as a FlexLogic entry, the associated state flag is never set to '1'. Press the +/– key when editing
FlexLogic equations to quickly scan through the major parameter types.
5

5.6.6 FlexLogic timers

SETTINGS  FLEXLOGIC  FLEXLOGIC TIMERS  FLEXLOGIC TIMER 1(32)
 FLEXLOGIC
 TIMER 1
There are 32 identical FlexLogic timers available. These timers are used as operators for FlexLogic equations.
— Selects the time measurement unit.
TIMER 1 TYPE
TIMER 1 PICKUP DELAY
TIMER 1 DROPOUT DELAY

5.6.7 FlexElements

SETTINGS  FLEXLOGIC  FLEXELEMENTS  FLEXELEMENT 1(16)
 FLEXELEMENT 1
5-202
FLEXLOGIC ENTRY 1:
END
FLEXLOGIC ENTRY 1024:
END
TIMER 1
TYPE: millisecond
TIMER 1 PICKUP
DELAY:
0
TIMER 1 DROPOUT
DELAY:
0
— Sets the time delay to pickup. If a pickup delay is not required, set this function to "0."
— Sets the time delay to dropout. If a dropout delay is not required, set this function to "0."
FLEXELEMENT 1
FUNCTION: Disabled
FLEXELEMENT 1 NAME:
FxE 1
FLEXELEMENT 1 +IN:
Off
FLEXELEMENT 1 -IN:
Off
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Range: FlexLogic operands
Range: FlexLogic operands
Range: millisecond, second, minute
Range: 0 to 60000 in steps of 1
Range: 0 to 60000 in steps of 1
Range: Disabled, Enabled
Range: up to six alphanumeric characters
Range: Off, any analog actual value parameter
Range: Off, any analog actual value parameter
CHAPTER 5: SETTINGS