SYSTEM SETUP
— This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch 1
SWITCH 1 OPEN
open command.
SWITCH 1 BLK OPEN
setting can be used to block the disconnect switch from opening, for instance when switchyard monitoring indicates that
current exceeding the switch's interrupting rating can be flowing through the switch.
— This setting selects an operand that when activated, and unless blocked, initiates the disconnect switch
SWITCH 1 CLOSE
1 close command.
SWITCH 1 BLK CLOSE
setting can be used to block the disconnect switch from closing, for instance to prevent closing into a closed ground
switch.
SWTCH 1 ΦA/3P CLSD
position tracking mechanism. This input is for a normally-open 89/a status input that creates a logic 1 when the
disconnect switch is closed. If the
the operand used to track the disconnect switch open or closed position. If the mode is selected as "1-Pole," the input
mentioned is used to track phase A and the
C, respectively.
SWTCH 1 ΦA/3P OPND
input that creates a logic 1 when the disconnect switch is open. If a separate 89/b contact input is not available, then an
inverted 89/a status signal can be used.
SWITCH 1 ΦB CLOSED
pole, this input is used to track the disconnect switch phase B closed position as outlined for phase A.
SWITCH 1 ΦB OPENED
pole, this input is used to track the disconnect switch phase B opened position as outlined for phase A.
5
SWITCH 1 ΦC CLOSED
pole, this input is used to track the disconnect switch phase C closed position as outlined for phase A.
SWITCH 1 ΦC OPENED
pole, this input is used to track the disconnect switch phase C opened position as outlined for phase A.
SWITCH 1 PUSH BUTTON CONTROL
SWITCH 1 TAGGING
operations are disabled:
Pushbutton Open/Close
IEC 61850 Open/Close
Open command initiated by
Close command initiated by
SWITCH 1 SUBSTITUTN
switch 1 control open/close status is forced to the substituted value.
—Set to "Enable" to allow the graphical front panel to bypass switch 1 interlocking. When asserted,
SWITCH 1 BYPASS
SWITCH 1 BLK OPEN
SWITCH 1 OPEN SEAL-IN
open command to the disconnect switch.
SWITCH 1 CLOSE SEAL-IN
close command to the disconnect switch.
SWITCH 1 TOPERATE
and 89/b auxiliary contacts during disconnect switch operation. If transient disagreement still exists after this time has
expired, the
SWITCH 1 BAD STATUS
SWITCH 1 ALARM DELAY
position tracking operands do not declare a pole disagreement. This allows for non-simultaneous operation of the poles.
5-154
— This setting selects an operand that prevents initiation of the disconnect switch 1 command. This
— This setting selects an operand that prevents initiation of disconnect switch 1 close commands. This
— This setting selects an operand, usually a contact input connected to a disconnect switch auxiliary
SWITCH 1 MODE
SWITCH 1 ΦB
— This setting selects an operand, usually a contact input, that is for a normally-closed 89/b status
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— Set to "Enable" to allow front panel pushbutton open/close control operations.
— Set to "Enable" to allow the graphical front panel to tag switch 1. When tagged, the following
SWITCH 1 OPEN
SWITCH 1 CLOSE
— Set to "Enable" to allow the graphical front panel to substitute switch 1 status. When substituted,
and
settings are bypassed.
SWITCH 1 BLK CLOSE
— This setting specifies the seal-in time of the open command due to an operator-initiated manual
— This setting specifies the seal-in time of the close command due to an operator-initiated manual
— This setting specifies the required interval to overcome transient disagreement between the 89/a
FlexLogic operand is asserted for alarm or blocking purposes.
— This setting specifies the delay interval during which a disagreement of status among the pole
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
setting is selected as "3-Pole," this setting selects a single 89/a input as
and
settings select operands to track phases B and
SWITCH 1 ΦC
setting
setting
CHAPTER 5: SETTINGS