CHAPTER 5: SETTINGS
Figure 5-74: Disconnect switch control graphical front panel logic (sheet 3 of 3)
5.5.6 FlexCurves
5.5.6.1 Settings
SETTINGS SYSTEM SETUP FLEXCURVES FLEXCURE A(D)
FLEXCURVE A
FlexCurves A through D have settings for entering times to reset and operate at the following pickup levels: 0.00 to 0.98
and 1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter
a custom FlexCurve, enter the reset and operate times (using the
up/down keys) for the required protection curve (A, B, C, or D).
MESSAGE
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
FLEXCURVE A TIME AT
0.00 xPKP:
0 ms
FLEXCURVE A TIME AT
0.05 xPKP:
0 ms
FLEXCURVE A TIME AT
20.00xPKP:
0 ms
Range: 0 to 65535 ms in steps of 1
Range: 0 to 65535 ms in steps of 1
Range: 0 to 65535 ms in steps of 1
keys) for each selected pickup point (using the
VALUE
SYSTEM SETUP
5
5-157