CHAPTER 7: COMMANDS AND TARGETS
FLEXLOGIC ERROR:
with 2nd line detail
Latched target message: No.
Description of problem: A FlexLogic equation is incorrect.
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
What to do: Finish all equation editing and use self tests to debug any errors.
UNIT NOT PROGRAMMED:
Check Settings
Latched target message: No.
Description of problem: The
programmed.
How often the test is performed: On power up and whenever the
setting is altered
.
What to do: Program all settings and then set
DIAGNOSTIC FAILURE___:
Self Test Error
Latched target message: No.
Description of problem: Internal recovery failure detected.
How often the test is performed: Continuous.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
SYSTEM FAILURE___:
with 2nd line detail
Latched target message: Yes.
Description of problem: Module hardware failure detected.
How often the test is performed: Module dependent.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
7.2.2.3 Minor self-test error messages
Most of the minor self-test errors can be disabled. See the settings in the User-programmable Self-tests section in chapter
5.
DIAGNOSTIC ALARM:
with 2nd line detail
Latched target message: Yes.
Description of problem: Internal process disruption detected.
How often the test is performed: Module dependent.
What to do: Extract a Service Report through UR Setup software. Contact technical support and supply details of the
failure code on the display.
MAINTENANCE ALERT:
Replace Battery
Latched target message: Yes.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
setting indicates the N60 is not
PRODUCT SETUP  INSTALLATION  RELAY SETTINGS
TARGETS MENU
.
to "Programmed."