GE N60 Instruction Manual page 376

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

SYSTEM SETUP
PMU AGGREGATOR 1 TCP PORT
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 UDP PORT
even those of unused aggregators, must be valid and unique to avoid port number collisions.
PMU AGGREGATOR 1 PDC CONTROL
be executed on the PMU. The control is accomplished via an extended command frame. The relay decodes the first word
of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator supports 16 FlexLogic
operands, as shown in the table. The operands are asserted for five seconds following reception of the command frame. If
the new command frame arrives within the five-second period, the FlexLogic operands are updated, and the five-second
timer restarts. This setting enables or disables the control. When enabled, all 16 operands for each aggregator are active;
when disabled, all 16 operands for each aggregator remain reset.
Table 5-21: FlexLogic operands supported by aggregator
Operand type
ELEMENT:
Synchrophasor, phasor data,
concentrator
as above
as above
as above
5
as above
as above
as above
as above
SETTINGS  SYSTEM SETUP  PHASOR MEASUREMENT UNIT  PMU AGGREGATOR 1(4)  90-5 AGGR 1(4)
CONFIGURATION
 90-5 AGGR 1
 CONFIGURATION
PMU AGGREGATOR 1 NAME
This value, concatenated with the Aggregator IDCode and Aggregator Class of Service, is mapped into the IEC 61850
MSVID filed in the output stream. The field allows 65 characters, but uses the first 56 characters.
AGGREGATOR 1: PHYSICAL PORT
transmitted. The range is 1, 2, 3.
PMU AGGREGATOR 1: UDP PORT
A default setting value for IEC 6150-90-5 is provided.
5-182
— Selects the TCP port number to be used by this aggregator for network reporting. All ports,
— Selects the UDP port number to be used by this aggregator for network reporting. All ports,
— The synchrophasor standard allows for user-defined controls originating at the PDC, to
Operand syntax
AGTR1 PDC CNTRL 1
AGTR1 PDC CNTRL 2
AGTR1 PDC CNTRL 3
AGTR1 PDC CNTRL 16
AGTR2 PDC CNTRL 1
AGTR2 PDC CNTRL 2
AGTR2 PDC CNTRL 3
AGTR1 PDC CNTRL 16
PMU AGGREGATOR 1
NAME:
PMU AGGREGATOR 1
PORT: 1
PMU AGGREGATOR 1
UDP PORT: 102
PMU AGGREGATOR 1
NUMBER OF ASDUs: 1
— A user-defined visible string of characters (maximum 56) to identify the source of the stream.
— This setting determines the physical ports through which the synchrophasor traffic is
— This setting selects the UDP port number that is used by this dataset for network reporting.
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Operand description
Phasor data concentrator asserts control bit 1, as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Phasor data concentrator asserts control bit 1 as
received via the network
Phasor data concentrator asserts control bit 2 as
received via the network
Phasor data concentrator asserts control bit 3 as
received via the network
Phasor data concentrator asserts control bit 16, as
received via the network
Range: 56-character ASCII text (blank by default)
Range: 1, 2, 3
Range: 0 to 65534 in steps of 1
Range: 1 to 4
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading