PRODUCT SETUP

5.3.15 User-programmable pushbuttons

SETTINGS  PRODUCT SETUP  USER-PROGRAMMABLE PUSHBUTTONS  USER PUSHBUTTON 1(16)
 USER PUSHBUTTON 1
5
5-124
Figure 5-54: Control pushbutton logic
PUSHBUTTON 1
FUNCTION: Disabled
PUSHBTN 1 ID TEXT:
USER PB 1
PUSHBTN 1 ON TEXT:
PUSHBTN 1 OFF TEXT:
PUSHBTN 1 HOLD:
0.0 s
PUSHBTN 1 SET:
Off
PUSHBTN 1 RESET:
Off
PUSHBTN 1 AUTORST:
Disabled
PUSHBTN 1 AUTORST
DELAY: 1.0 s
PUSHBTN 1 REMOTE:
Off
PUSHBTN 1 LOCAL:
Off
PUSHBTN 1 DROP-OUT
TIME: 0.00 s
PUSHBTN 1 LED CTL:
Off
PUSHBTN 1 MESSAGE:
Disabled
PUSHBUTTON 1
EVENTS: Disabled
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
Range: Self-Reset, Latched, Disabled
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: up to 20 alphanumeric characters
Range: 0.0 to 10.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: Disabled, Enabled
Range: 0.2 to 600.0 s in steps of 0.1
Range: FlexLogic operand
Range: FlexLogic operand
Range: 0 to 60.00 s in steps of 0.05
Range: FlexLogic operand
Range: Disabled, Normal, High Priority
Range: Disabled, Enabled