PRODUCT SETUP
A command or setting write operation is required to update the state of the remote and local security operands
listed.
When a setting password or command password is set or updated, user access with a graphical front panel is
removed. Simply log in again on the graphical front panel.
When the setting password is set or updated, the graphical front panel Access Level displays as Command. This is
because the graphical front panel is a Modbus client and it does not have automatic access to the password
change.
PASSWORD ACCESS EVENTS
Change local passwords
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE LOCAL PASSWORDS
 CHANGE LOCAL
 PASSWORDS
As outlined in the previous section, there are two user security access levels, setting and command. Use of a password for
each level controls whether users can enter commands or change settings.
Proper password codes are required to enable each access level. When a
SETTING PASSWORD
invoked:
5
1.
ENTER NEW PASSWORD: ____________.
2.
VERIFY NEW PASSWORD: ____________.
3.
NEW PASSWORD HAS BEEN STORED.
To gain write access to a "Restricted" setting, program the
then change the setting, or attempt to change the setting and follow the prompt to enter the programmed password. If the
password is correctly entered, access is allowed. Access automatically reverts to the "Restricted" level according to the
access level timeout setting values and when power is cycled.
If the setting and command passwords are identical, then this one password allows access to both commands and
settings.
If a remote connection is established, local passcodes are not visible.
Change remote passwords
Proper passwords are required to enable each command or setting level access, which are explained in the previous
section.
SETTINGS  PRODUCT SETUP  SECURITY  CHANGE REMOTE PASSWORDS
 CHANGE REMOTE
 PASSWORDS
To set the command or setting password in EnerVista:
1.
In the EnerVista software or from the front panel, navigate to Settings > Product Setup > Security menu item to open
the remote password settings window.
2.
Click the command or setting password Change button.
3.
Enter the new password in the New Password field. Requirements are outlined in the Password Requirements section
earlier in this chapter. When an original password has already been used, enter it in the Enter Password field and click
5-10
— This setting allows recording of password access events in the event recorder.
CHANGE SETTING
PASSWORD: No
CHANGE COMMAND
PASSWORD: No
setting is programmed to "Yes" via the front panel interface, the following message sequence is
CHANGE SETTING
PASSWORD: No
CHANGE COMMAND
PASSWORD: No
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
Range: No, Yes
Range: No, Yes
CHANGE COMMAND PASSWORD
setting in the main security menu to "Setting" and
ACCESS LEVEL
Range: No, Yes
Range: No, Yes
CHAPTER 5: SETTINGS
or
CHANGE