GE N60 Instruction Manual page 300

Network stability and synchrophasor
Hide thumbs Also See for N60:
Table of Contents

Advertisement

PRODUCT SETUP
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 COMMANDS
 IEC103 COMMANDS
 COMMAND 0
 COMMAND 31
5
Commands are received as General Command (Type Identification 20). The user can configure the action to perform when
an ASDU command comes.
A list of available mappings is provided on the N60. This includes 64 virtual inputs (see the following table). The ON and OFF
for the same ASDU command can be mapped to different virtual inputs.
Each command is identified by the unique combination made by the function type (FUN) and information number (INF). If
the master sends an ASDU command that does not have the FUN and INF of any configured command, the relay rejects it.
Table 5-12: Commands mapping table
Description
Off
Virtual Input 1
Virtual Input 2
...
Virtual Input 64
For any change to take effect, restart the relay.
5.3.5.17 USB port
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  USB 2.0
 USB 2.0
5-106
 COMMAND 0
 COMMAND 1
 COMMAND 31
COMMAND 0 FUN:
0
COMMAND 0 INF:
0
COMMAND 0 ON:
Off
COMMAND 0 OFF:
Off
COMMAND 31 FUN:
0
COMMAND 31 INF:
0
COMMAND 31 ON:
Off
COMMAND 31 OFF:
Off
Value
0
1
2
...
64
USB DEVICE PORT
FUNCTION: Enabled
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
See below
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: Virtual input
Range: Virtual input
Range: Disabled, Enabled
CHAPTER 5: SETTINGS

Advertisement

Table of Contents
loading

Table of Contents