CHAPTER 5: SETTINGS
5.7 Grouped elements
5.7.1 Overview
Each protection element can be assigned up to six sets of settings with designations 1 to 6. The performance of these
elements is defined by the active setting group at a given time. Multiple setting groups allow the user to conveniently
change protection settings for different operating situations (for example, altered power system configuration or season of
the year). The active setting group can be preset or selected in the
later in this chapter). See also the Introduction to Elements section at the beginning of this chapter.
5.7.2 Setting group 1
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6)
SETTING GROUP 1
Each of the six setting group menus is identical. Setting group 1 (the default active group) is active automatically when no
other group is active.
If the device incorrectly switches to group 1 after power cycling, upgrade the firmware to version 7.31 or later to correct
this issue.
5.7.3 Power swing detect (ANSI 68)
SETTINGS GROUPED ELEMENTS SETTING GROUP 1(6) POWER SWING DETECT
POWER SWING
DETECT
N60 NETWORK STABILITY AND SYNCHROPHASOR MEASUREMENT SYSTEM – INSTRUCTION MANUAL
POWER SWING
DETECT
PHASE CURRENT
NEUTRAL CURRENT
GROUND CURRENT
VOLTAGE ELEMENTS
SUPERVISING
ELEMENTS
POWER
POWER SWING
FUNCTION: Disabled
POWER SWING
SOURCE: SRC 1
POWER SWING
SHAPE: Mho Shape
POWER SWING
MODE: Two Step
POWER SWING
SUPV: 0.600 pu
POWER SW I2 SUPV ENAB:
Off
menu (see the Control Elements section
SETTING GROUPS
See below
See page 5-221
See page 5-233
See page 5-241
See page 5-244
See page 5-247
See page 5-249
Range: Disabled, Enabled
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
Range: Mho Shape, Quad Shape
Range: Two Step, Three Step
Range: 0.050 to 30.000 pu in steps of 0.001
Range: FlexLogic operand
GROUPED ELEMENTS
5
5-211