Establishing connection and verifying the IEEE C37.118/1344 communication
Section 9
9.1
9.2
Commissioning manual
Establishing connection and verifying the
IEEE C37.118/1344 communication

Overview

The IED can support synchrophasor data communication via IEEE C37.118 and/or
IEEE1344 with maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can
also be used for substation bus (IEC 61850-8-1) communication and process bus (IEC
61850-9-2LE) communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an
Ethernet communication link (e.g. optical fiber) shall be available and the required
parameters on both PMU and the TCP/UDP client shall be set. For the purpose of this
section, an Open PDC tool (PMU Connection Tester) installed on a PC is used as the TCP/
UDP client.

Setting the PMU station communication (PMU Report)

1.
Check the settings for the PMU Report parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Report/PMUREPORT:1
1.1. Make sure that the operation of at least one PMU instance (e.g. PMU1) is
Enabled.
1.2. Enable sending the frequency data by setting the parameter SendFreqInfo to
Enabled.
2.
Check the operation of the required phasor channels (PHASORREPORT) by
navigating to: Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PHASORREPORT:x.
Section 9
65