Table 16:
Self-supervision signals on the local HMI
HMI Signal Name:
Status
INT Fail
OFF / ON
INT Warning
OFF / ON
ADMnn
READY / FAIL
BIMnn
READY / FAIL
BOMn
READY / FAIL
IOMn
READY / FAIL
MIMn
READY / FAIL
RTC
READY / FAIL
Time Sync
READY / FAIL
Application
READY / FAIL
RTE
READY / FAIL
IEC61850
READY / FAIL
LMD
READY / FAIL
LDCMxxx
READY / FAIL
OEM
READY / FAIL
Description
This signal will be active if one or more of
the following internal signals are active;
INT--LMDERROR, INT--WATCHDOG,
INT--APPERROR, INT--RTEERROR, or
any of the HW dependent signals
This signal will be active if one or more of
the following internal signals are active;
INT--RTCERROR, INT--
IEC61850ERROR, INT--
TIMESYNCHERROR
Analog input module n failed. Signal
activation will reset the IED
BIM error. Binary input module Error
status. Signal activation will reset the IED
BOM error. Binary output module Error
status.
IOM-error. Input/Output Module Error
status.
mA input module MIM1 failed. Signal
activation will reset the IED
This signal will be active when there is a
hardware error with the real time clock.
This signal will be active when the source
of the time synchronization is lost, or when
the time system has to make a time reset.
This signal will be active if one or more of
the application threads are not in the state
that Runtime Engine expects. The states
can be CREATED, INITIALIZED,
RUNNING, etc.
This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
This signal will be active if the IEC61850
stack did not succeed in some actions like
reading IEC61850 configuration, startup
etc.
LON network interface, MIP/DPS, is in an
unrecoverable error state.
Line Differential Communication Error
status
Optical Ethernet Module error status.