Section 13
Troubleshooting
178
UDPCtrlConnCnt4
UDPStreamStat5
UDPCtrlConnCnt5
UDPStreamStat6
UDPCtrlConnCnt6
UDPCtrlDataErrCnt
UDPCtrlCfgErrCnt
The following describes the various output states:
•
PMUInst1, PMUInst2 – The outputs on these channels show the status of the two
available PMUREPORT instances.
Each status output has the following states:
•
Off – When the component is not in operation.
•
Ready – when it is sending data based on the configuration.
•
ConfigError – if same PMU Id is used for both the instances.
•
Data Invalid – when the PMU is producing an invalid data stream and the data
from it cannot be trusted.
•
TCPConnStatus1-8 – The 8 TCP connection status outputs show if there is an active
TCP connection or not. Each status output has the following states:
•
Off - No active connection.
•
Active - A client is connected and receiving data.
•
TCPCtrlDataErrCnt - The output shows the number of times the PMU has failed to
send the configuration frame, header frames or data frame on C37.118 or IEEE1344.
•
TCPCtrlCfgErrCnt - The outputs show the number of errors that have occurred due
to incorrect configuration request by the client. These errors can be due to client
trying to send a wrong PMUId on this link than the one that is configured, or trying
to request an IEEE1344 configuration on C37.118 channel.
•
UDPStreamStat1-6 - The six UDP stream status outputs have the following states:
Number of UDP control client connected on
0 to 4
UDP Group4
Off
Active
Config Error
UDP data stream status for UDP Group5
Off by client
Client unreachable
Number of UDP control client connected on
0 to 4
UDP Group5
Off
Active
Config Error
UDP data stream status for UDP Group6
Off by client
Client unreachable
Number of UDP control client connected on
0 to 4
UDP Group6
Number of times IED has failed to respond for
0 to 4294967295
a command requested on C37.118 or
IEEE1344 over TCP control for UDP
Number of errors that have occurred due to
0 to 4294967295
incorrect configuration request by the client
over TCP control for UDP
1MRK 511 366-UUS -
Commissioning manual