ABB RES670 2.1 Commissioning Manual page 184

Phasor measurement unit
Table of Contents

Advertisement

Section 13
Troubleshooting
178
UDPCtrlConnCnt4
UDPStreamStat5
UDPCtrlConnCnt5
UDPStreamStat6
UDPCtrlConnCnt6
UDPCtrlDataErrCnt
UDPCtrlCfgErrCnt
The following describes the various output states:
PMUInst1, PMUInst2 – The outputs on these channels show the status of the two
available PMUREPORT instances.
Each status output has the following states:
Off – When the component is not in operation.
Ready – when it is sending data based on the configuration.
ConfigError – if same PMU Id is used for both the instances.
Data Invalid – when the PMU is producing an invalid data stream and the data
from it cannot be trusted.
TCPConnStatus1-8 – The 8 TCP connection status outputs show if there is an active
TCP connection or not. Each status output has the following states:
Off - No active connection.
Active - A client is connected and receiving data.
TCPCtrlDataErrCnt - The output shows the number of times the PMU has failed to
send the configuration frame, header frames or data frame on C37.118 or IEEE1344.
TCPCtrlCfgErrCnt - The outputs show the number of errors that have occurred due
to incorrect configuration request by the client. These errors can be due to client
trying to send a wrong PMUId on this link than the one that is configured, or trying
to request an IEEE1344 configuration on C37.118 channel.
UDPStreamStat1-6 - The six UDP stream status outputs have the following states:
Number of UDP control client connected on
0 to 4
UDP Group4
Off
Active
Config Error
UDP data stream status for UDP Group5
Off by client
Client unreachable
Number of UDP control client connected on
0 to 4
UDP Group5
Off
Active
Config Error
UDP data stream status for UDP Group6
Off by client
Client unreachable
Number of UDP control client connected on
0 to 4
UDP Group6
Number of times IED has failed to respond for
0 to 4294967295
a command requested on C37.118 or
IEEE1344 over TCP control for UDP
Number of errors that have occurred due to
0 to 4294967295
incorrect configuration request by the client
over TCP control for UDP
1MRK 511 366-UUS -
Commissioning manual