ABB RES670 2.1 Commissioning Manual page 113

Phasor measurement unit
Table of Contents

Advertisement

1MRK 511 366-UUS -
Commissioning manual
the point RE (R
a point which is related to the parameter ReachZ1 (boundary between zone 1
and zone 2)
the point SE (R
The phase angle of the test voltages is equal to:
arctan (ForwardX/ForwardR) for tests in the quadrant 1 and 2 of the R-X plane
arctan (ReverseX/ReverseR) -180° for tests in the quadrant 3 and 4 of the R-X plane
Symmetric three-phase current, where the current is the summation of two currents
that have the same magnitude, but different frequencies.
I
20918
t
I
I
=
=
=
50
tf
2
2
GUID-F02E8D18-FF87-45BE-8142-E8FA19F6966B V1 EN
The first current I
50
secondary) and phase angle 0º.
The second current I
angle 180º (at the starting time of the test) and frequency:
49.5 Hz for the test as generator in the quadrant 1 and 2 of the R-X plane
50.5 Hz for the test as generator in the quadrant 3 and 4 of the R-X plane
When the trajectory of the impedance, that is seen by the protection
function, traverses the lens characteristic then a pole slipping is detected.
The present procedure avoids tests of points of the line SE-RE that are too
close to the R-axis because in that case the voltage is close to zero and,
therefore, the impedance may approach a not defined quantity 0/0.
The accuracy of the impedance reach is ±2% of the base impedance; that
is considered while evaluating the test results.
For the test as motor the frequency current may have 50.5 Hz in the
quadrant 1 and 2 of the R-X plane and 49.5 Hz in the quadrant 3 and 4.
Testing functionality by secondary injection
, X
)
FwdR
FwdX
, X
)
RvsR
RvsX
A
10459
=
has frequency 50 Hz, magnitude 10459 A (that is, 1.162 A
has magnitude 10459 A (that is, 1.162 A secondary), phase
tf
Section 11
(Equation 16)
107

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion670 seriesRelion 670 seriesRelion res670

Table of Contents