Communication Diagnostics - ABB RES670 2.1 Commissioning Manual

Phasor measurement unit
Table of Contents

Advertisement

Section 13
Troubleshooting
13.1.2.2
174
Indicated result
Possible reason
Real time clock Ready
No problem detected.
Real time clock Fail
The real time clock has
been reset.
ADC-module OK
No problem detected.
ADC-module Fail
The AD conversion
module has failed.
(Protocol name) Ready
No problem detected.
(Protocol name) Fail
Protocol has failed.
(I/O module name)
No problem detected.
Ready
(I/O module name) Fail
I/O modules has failed.

Communication Diagnostics

All the communications in the IED (Front port and rear LAN AB/CD ports) can be
supervised via the local HMI under Main menu/Diagnostics/Communication.
IEC140000115 V1 EN
Figure 32:
The PMU communication diagnostic menu
1MRK 511 366-UUS -
Proposed action
None.
Set the clock.
None.
Contact your ABB representative for service.
None.
None.
Check that the I/O module has been configured and
connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
IEC140000115-2-en.vsd