1MRK 511 366-UUS -
Commissioning manual
Off - UDP data stream is turned off.
Active – UDP data stream is on.
ConfigError – When the stream is set to send a stream from PMU instance not
instantiated in ACT.
Off by client – UDP data stream is turned off by an external client.
Client Unreachable – Unable to send data to configured client, or host
unreachable.
UDPCtrlConnStatus1-6 – The 6 UDP stream control connection status output, shows
the number of concurrent clients connected to control the UDP data stream. A
maximum of 4 clients can be connected concurrently.
UDPCtrlDataErrCnt - The output shows the number of times IED has failed to
respond for a command requested on C37.118 or IEEE1344.
UDPCtrlCfgErrCnt - The output shows the number of errors that have occurred due
to incorrect configuration request by the client. These errors can be due to client
trying to send a wrong PMUId on this link than the one configured, or trying to
request an IEEE1344 configuration on C37.118 channel.
The PMUSTATUS output signals can also be mapped on DNP3.0 protocol. Table
shows the different numbers corresponding to different output statuses.
Table 15:
The PMUSTATUS output signals mapped on DNP3.0 protocol
PMU Diagnostic Output
PMUInst1
PMUInst2
TCPConnStatus1
TCPConnStatus2
TCPConnStatus3
TCPConnStatus4
TCPConnStatus5
TCPConnStatus6
TCPConnStatus7
Table continues on next page
Status
DNP3.0 Mapping
Off
0
Ready
1
Config Error
2
Data Invalid
3
Off
0
Ready
1
Config Error
2
Data Invalid
3
Off
0
Active
1
Off
0
Active
1
Off
0
Active
1
Off
0
Active
1
Off
0
Active
1
Off
0
Active
1
Off
0
Active
1
Section 13
Troubleshooting
15
179